Finding Type
Odors
Remediation
Building Services is to review the ventilation unit's outdoor air damper sequence to ensure operation and receiving minimal outdoor air (assists with the dilution of human occupancy).
Building Service is to evaluate the variable air volume boxes (i.e. dampers) where there is question as to the reduced air volume in the front office reception area.
Location
A122
Tracking Number
FXLRHS201900116A
Assigned To
Building Services
Work Orders
#113649
(In Progress)
Closed
No