Finding: Bollman Bridge Elementary School: Gym Office (FXBBES2022001FAC)

Finding Type
Miscellaneous finding
Remediation

Building Maintenance closed the outdoor air dampers to the unit (gym offices unoccupied as staff had not returned from summer break) and changed the fan setting to reduce the amount of outdoor air supplied. The temperature was also adjusted to reduce relative humidity. A precautionary cleaning of the unit was also completed.

The Office of the Environment requested that Building Maintenance (HVAC) create an annual re-occurring work order to adjust the setpoint, outdoor air dampers, and fan setting at the end of the school  year as a preventative measure. Another re-occurring work order will be created to return the settings when staff/students return. 

Location
Gym Office
Tracking Number
FXBBES2022001FAC
Assigned To
Environmental Services
Closed
Yes
Completion Date