Concern: Wilde Lake High School: August 27th, 2018 (CXWLHS2018000015)

Location
234
Date of IEQ Report Form
Date of Report
Concern
Individual concerned that mold growth may be behind the wood cabinets associated with the science lab stations because there were water leaks in this area last year.
IEQ Investigation Process

Identify deficiencies that may impact IEQ and/or sources of odor concerns. Typically includes the following depending on the nature of concern, but not limited to:

  • interview/questionnaire of concern individual(s)
  • inspection above drop ceiling (condition of roof deck, pipe insulation, return air plenum)
  • inspection of ventilation system (operation of variable air volume box and outdoor air dampers, check controls, measurements of carbon dioxide, temperature and relative humidity, sources near outdoor air intake, measure return and supply air volume, cleanliness of coils, liner and condensate pan)
  • inspection of exterior
  • inspection below drop ceiling (housekeeping, sink and floor drain traps, signs of past and present moisture concern via visual and/or moisture meter, mold growth, ensure connection of current and capping of abandoned sanitary vents, odorizers, excessive plants and fabric items, identify potential pathways, and measure volatile organic compounds, carbon monoxide, and lighting)
Findings

Date of Investigation:  August 30, 2018

Access points under the lab station(s) allowed for chases to be inspected with the use of flashlight and mirror.

No visible mold growth was observed on wood surfaces within the chases or cabinets under areas in question.

No further action appears to be required.

Closed
Yes
Date Closed
Tracking Number
CXWLHS2018000015