Indoor Environmental Quality HVAC Assessment of Homewood Center: March 3rd, 2021 (HXXXHC202100003A)

Assessor
Hummy Khan
Date
Outdoor Temperature
52°F
Relative Humidity
23%
Outdoor Dew Point
17°F

Air Handling Unit (Assess representative sample of RTU/AHU, including Portables)

Unit
Check OK Comments
Tag Number
Displayed
No
No tag numbers on any exhaust fans.
Status
Running
Yes
Outdoor Air Intake and Outdoor Air Dampers
Check OK Comments
Outdoor Pollution
Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
Yes
Louvers and Access Doors
Operating properly
Yes
Deflectors & Screens
Present
Yes
No debris
Yes
Dampers
Outside air damper: no obstructions
No
AHU-6 and AHU-7- Outside air dampers closed.
Return air damper: no obstructions
No
AHU-2, AHU-3 and AHU-4 - Bigger section of return air dampers appear to be closed but the smaller section appears to open and on AHU-1, AHU-5, AHU-6 and AHU-7 it is the opposite.
Mixing Plenum
Check OK Comments
Clean
No excess dirt, not used for storage
No
AHU-6 - Several actuators stored in mixing plenum.
Insulation
Secure and Clean
Yes
P-Trap (if present)
Charged with liquid
Yes
Filters and Coils
Check OK Comments
Filters
Free of any bypassing
No
AHU-1 and AHU-5 - Air bypass around air filters
Correct size
Yes
Free from excessive loading, dampness or odor
Yes
Not collapsed/not fallen off
No
AHU-1-Prefilter fallen off, reinstalled it while on site.
Present (not missing)
No
AHU-1-Final filter missing.
Date and initials written
No
No initials on any filters of the installing technician.
Heating Coils
Clean, no noticeable leaks, or obstructions
Yes
Cooling Coils
Clean, no noticeable leaks, or obstructions
Yes
Access: Free of any obstructions in area that may affect access
Yes
Condensation: No excess condensation problems
Yes
Blowoff: Free of water from coil blowoff
Yes
Condensate Pan and Drain Line
No visible bacterial or fungal growth
Yes
Clean, no residue, no standing water
Yes
No Overflow, leakage, blockage, or damage
Yes
Proper slope, drain line ok, drainage acceptable, discharge okay
Yes
Fans and Motors
Check OK Comments
Condition
Operational
Yes
No unusual odors, noise, or vibration
Yes
Central Plant
Check OK Comments
Chilled Water Central Plant
Chiller operational
Yes
Not operational due to heating season.
Heating Central Plant
Boiler operational
Yes
Portable(s)
Check OK Comments
Thermostat
Thermostat setting acceptable
No
Portable 201- Thermostat in "Hold" mode instead of running on programmed schedule and needs to be programmed first. Informed the HVAC department about this while on site.
Thermostat cover
Yes
Fan Mode Correct
Yes
Space Temperature Acceptable
Yes
Misc. Comments
Work Order: 183726
Work Order Number(s)
183726
Issues found durring this assessment have been assigned to the above work order(s).