School
Assessor
Hummy Khan
Date
Outdoor Temperature
39°F
Relative Humidity
52%
Outdoor Dew Point
23°F
Air Handling Unit (Assess representative sample of RTU/AHU, including Portables)
Check | OK | Comments |
---|---|---|
Tag Number | ||
Displayed
|
No
|
Some of the exhaust fans do not have tag numbers.
|
Status | ||
Running
|
No
|
Kitchen Unit - Not operational.
|
Check | OK | Comments |
---|---|---|
Outdoor Pollution | ||
Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
|
Yes
|
|
Louvers and Access Doors | ||
Operating properly
|
Yes
|
|
Deflectors & Screens | ||
Present
|
Yes
|
|
No debris
|
Yes
|
|
Dampers | ||
Outside air damper: no obstructions
|
Yes
|
|
Return air damper: no obstructions
|
Yes
|
Check | OK | Comments |
---|---|---|
Clean | ||
No excess dirt, not used for storage
|
Yes
|
|
Insulation | ||
Secure and Clean
|
Yes
|
|
P-Trap (if present) | ||
Charged with liquid
|
Yes
|
Check | OK | Comments |
---|---|---|
Filters | ||
Free of any bypassing
|
No
|
Carrier RAHU-3- Air bypass.
|
Correct size
|
No
|
Carrier RAHU-4 - Lower grade mesh screen filter installed on one rack.
|
Free from excessive loading, dampness or odor
|
Yes
|
|
Not collapsed/not fallen off
|
No
|
DOAS # 7 - Filter bent in outside air section. DOAS #8 - Filters bent.
|
Present (not missing)
|
No
|
Kitchen Unit - Filters missing. Carrier RAHU-3 and 4 - Pre-filters missing from one rack and final filters missing from another rack.
|
Date and initials written
|
Yes
|
|
Heating Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Cooling Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Access: Free of any obstructions in area that may affect access
|
Yes
|
|
Condensation: No excess condensation problems
|
Yes
|
|
Blowoff: Free of water from coil blowoff
|
Yes
|
|
Condensate Pan and Drain Line | ||
No visible bacterial or fungal growth
|
Yes
|
|
Clean, no residue, no standing water
|
Yes
|
|
No Overflow, leakage, blockage, or damage
|
Yes
|
|
Proper slope, drain line ok, drainage acceptable, discharge okay
|
No
|
Carrier RAHU-4 and DOAS # 5 - Condensate drain line broken and laying on roof.
|
Check | OK | Comments |
---|---|---|
Condition | ||
Operational
|
No
|
Exhaust Fans #7, 8 and 11 - Not running.
|
No unusual odors, noise, or vibration
|
Yes
|
Check | OK | Comments |
---|---|---|
Chilled Water Central Plant | ||
Chiller operational
|
Yes
|
Off due to the heating season.
|
Heating Central Plant | ||
Boiler operational
|
Yes
|
Misc. Comments
Work Order: 176113
Work Order Number(s)
176113
Issues found durring this assessment have been assigned to the above
work order(s).