Indoor Environmental Quality HVAC Assessment of Reservoir High School: November 11th, 2021 (HXXRHS2021000058)

Assessor
Hummy Khan
Date
Outdoor Temperature
61°F
Relative Humidity
63%
Outdoor Dew Point
48°F

Air Handling Unit (Assess representative sample of RTU/AHU, including Portables)

Unit
Check OK Comments
Tag Number
Displayed
Yes
Work Order Closed by Building Maintenance
No tag numbers on any exhaust fans.
Status
Running
Yes
Outdoor Air Intake and Outdoor Air Dampers
Check OK Comments
Outdoor Pollution
Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
Yes
Louvers and Access Doors
Operating properly
Yes
Deflectors & Screens
Present
Yes
No debris
Yes
Dampers
Outside air damper: no obstructions
Yes
Work Order Closed by Building Maintenance
OAHU-2 and OAHU-4- A portion of the outside air dampers appeared to be 100% closed. These are dedicated outside air units and should be capable of bringing in100% outside air all the time while running. AHU-3 and AHU-5 - Outside air dampers (OADs) appeared to be closed. AHU-6- OADs are open but only slightly. There seems to be a lot of inconsistency on the position of the outside air dampers. Some are completely closed while others are more open. Today's outdoor weather conditions are ideal for the economizer mode, meaning the OADs should be open more than the minimum position up to 100%.
Return air damper: no obstructions
Yes
Mixing Plenum
Check OK Comments
Clean
No excess dirt, not used for storage
Yes
Insulation
Secure and Clean
Yes
P-Trap (if present)
Charged with liquid
Yes
Filters and Coils
Check OK Comments
Filters
Free of any bypassing
Yes
Work Order Closed by Building Maintenance
AHU-5- Air bypass around filters.
Correct size
Yes
Free from excessive loading, dampness or odor
Yes
Not collapsed/not fallen off
Yes
Work Order Closed by Building Maintenance
OAHU-2 and OAHU-4- Filter fallen off. Tried to put it back on but was not able to do so properly because it is bent. Filter clips missing in OAHU-4.
Present (not missing)
Yes
Date and initials written
Yes
Heating Coils
Clean, no noticeable leaks, or obstructions
Yes
Cooling Coils
Clean, no noticeable leaks, or obstructions
Yes
Access: Free of any obstructions in area that may affect access
Yes
Condensation: No excess condensation problems
Yes
Blowoff: Free of water from coil blowoff
Yes
Condensate Pan and Drain Line
No visible bacterial or fungal growth
Yes
Clean, no residue, no standing water
Yes
No Overflow, leakage, blockage, or damage
Yes
Proper slope, drain line ok, drainage acceptable, discharge okay
Yes
Fans and Motors
Check OK Comments
Condition
Operational
Yes
Work Order Closed by Building Maintenance
Exhaust fan (no tag number) located near OAHU-3 - Not running.
No unusual odors, noise, or vibration
Yes
Work Order Closed by Building Maintenance
Exhaust fan (no tag number) located near AHU-6 and another exhaust near cooling tower - Excessive vibration.
Central Plant
Check OK Comments
Chilled Water Central Plant
Chiller operational
Yes
Cooling tower operational
Yes
Heating Central Plant
Boiler operational
Yes
Portable(s)
Check OK Comments
Thermostat
Thermostat setting acceptable
Yes
Thermostat cover
Yes
Fan Mode Correct
Yes
Space Temperature Acceptable
Yes
Work Order Number(s)
215031
Issues found durring this assessment have been assigned to the above work order(s).