School
Assessor
Hummy Khan
Date
Outdoor Temperature
66°F
Relative Humidity
63%
Outdoor Dew Point
54°F
Air Handling Unit (Assess representative sample of RTU/AHU, including Portables)
Check | OK | Comments |
---|---|---|
Tag Number | ||
Displayed
|
Yes Work Order Closed by Building Maintenance
|
The Trane Voyager rooftop unit close to the roof access does not appear to a have tag number.
|
Status | ||
Running
|
Yes Work Order Closed by Building Maintenance
|
Rooftop unit (RTU-14) - Not running. Building Maintenance (HVAC) informed same day as discovery.
|
Check | OK | Comments |
---|---|---|
Outdoor Pollution | ||
Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
|
Yes
|
|
Louvers and Access Doors | ||
Operating properly
|
Yes Work Order Closed by Building Maintenance
|
RTU-17- Outside air section access door latch severely bent.
|
Deflectors & Screens | ||
Present
|
Yes
|
|
No debris
|
Yes
|
|
Dampers | ||
Outside air damper: no obstructions
|
Yes Work Order Closed by Building Maintenance
|
Inconsistency on the position of the outside air dampers (OADs) from one unit to the other. On some units, the OADs appear to be 100% open, while on others they are partially open when compared to similar types of units. For example:
• RTU-18 OADs are 100% open. At the time of walkthrough the outside temperature was approximately 66 deg. The OADs should not be 100% open at that temperature, it is too cold.
• RTU-16 – OADs are less open in comparison.
The OADs were observed to be 100% closed on the following units:
• RTU-# 4, RTU-7 and RTU-20
|
Return air damper: no obstructions
|
Yes
|
Check | OK | Comments |
---|---|---|
Clean | ||
No excess dirt, not used for storage
|
Yes Work Order Closed by Building Maintenance
|
Trane Voyager Rooftop HVAC Unit (No tag number) - Dirty mixing air plenum section.
|
Insulation | ||
Secure and Clean
|
Yes
|
|
P-Trap (if present) | ||
Charged with liquid
|
Yes
|
Check | OK | Comments |
---|---|---|
Filters | ||
Free of any bypassing
|
Yes
|
|
Correct size
|
Yes
|
|
Free from excessive loading, dampness or odor
|
Yes
|
|
Not collapsed/not fallen off
|
Yes
|
|
Present (not missing)
|
Yes
|
|
Date and initials written
|
Yes
|
|
Heating Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Cooling Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Access: Free of any obstructions in area that may affect access
|
Yes
|
|
Condensation: No excess condensation problems
|
Yes
|
|
Blowoff: Free of water from coil blowoff
|
Yes
|
|
Condensate Pan and Drain Line | ||
No visible bacterial or fungal growth
|
Yes
|
|
Clean, no residue, no standing water
|
Yes
|
|
No Overflow, leakage, blockage, or damage
|
Yes Work Order Closed by Building Maintenance
|
RTU-2 - Broken condensate drain pipe.
On RTU-8, RTU-9 and RTU-10, condensate drain improperly terminated, repeat finding.
|
Proper slope, drain line ok, drainage acceptable, discharge okay
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Operational
|
Yes
|
|
No unusual odors, noise, or vibration
|
Yes
|
Check | OK | Comments |
---|---|---|
Heating Central Plant | ||
Boiler operational
|
Yes
|
Check | OK | Comments |
---|---|---|
Thermostat | ||
Thermostat setting acceptable
|
Yes Work Order Closed by Building Maintenance
|
Portable # 127- Thermostat display screen blank.
|
Thermostat cover
|
Yes
|
|
Fan Mode Correct
|
Yes
|
|
Space Temperature Acceptable
|
Yes
|
Misc. Comments
Hammond Middle School and Hammond Elementary School are within the same building and some components of the HVAC systems are common to both schools. The findings reported here are also reported under Hammond Elementary School.
Work Order Number(s)
21909
Issues found durring this assessment have been assigned to the above
work order(s).