School
| Check | OK | Comments |
|---|---|---|
| Tag Number | ||
Displayed
|
Yes
|
|
| Status | ||
Running
|
Yes
|
OAU 3 exterior duct (gap in connecting sections) and insulation has damage which is blowing / leaking out supply air.
|
| Check | OK | Comments |
|---|---|---|
| Outdoor Pollution | ||
Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
|
Yes
|
|
| Louvers and Access Doors | ||
Operating properly
|
Yes
|
|
| Deflectors & Screens | ||
Present
|
Yes
|
|
No debris
|
Yes
|
|
| Dampers | ||
Outside air damper: no obstructions
|
Yes
|
|
Return air damper: no obstructions
|
Yes
|
|
Assessor
Jeffrey Klenk
Date
| Check | OK | Comments |
|---|---|---|
| Clean | ||
No excess dirt, not used for storage
|
Yes
|
|
| Insulation | ||
Secure and Clean
|
Yes
|
|
| P-Trap (if present) | ||
Charged with liquid
|
Yes
|
|
Outdoor Temperature
62°F
| Check | OK | Comments |
|---|---|---|
| Filters | ||
Free of any bypassing
|
Yes
|
|
Correct size
|
Yes
|
|
Free from excessive loading, dampness or odor
|
Yes
|
|
Not collapsed/not fallen off
|
Yes Work Order Closed by Building Maintenance
|
RTU 1 - Some air filters are out of their housing.
|
Present (not missing)
|
Yes
|
|
Date and initials written
|
Yes
|
|
| Heating Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes Work Order Closed by Building Maintenance
|
RTU 1 - Coils have an area of accumulated particulate.
|
| Cooling Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes Work Order Closed by Building Maintenance
|
RTU 1 - Coils have an area of accumulated particulate.
|
Access: Free of any obstructions in area that may affect access
|
Yes
|
|
Condensation: No excess condensation problems
|
Yes
|
|
Blowoff: Free of water from coil blowoff
|
Yes
|
|
| Condensate Pan and Drain Line | ||
No visible bacterial or fungal growth
|
Yes
|
|
Clean, no residue, no standing water
|
Yes
|
|
No Overflow, leakage, blockage, or damage
|
Yes Work Order Closed by Building Maintenance
|
OAHU-1 and 2 - The exterior PVC condensate drains are intact, but minor leaks (signs of future deterioration) in connections.
|
Proper slope, drain line ok, drainage acceptable, discharge okay
|
Yes
|
|
Relative Humidity
80%
| Check | OK | Comments |
|---|---|---|
| Condition | ||
Operational
|
Yes
|
|
No unusual odors, noise, or vibration
|
Yes
|
|
Outdoor Dew Point
56°F
| Check | OK | Comments |
|---|---|---|
| Heating Central Plant | ||
Boiler operational
|
Yes
|
|
Work Order Number(s)
234468, 234472, 234462
Issues found durring this assessment have been assigned to the above
work order(s).
Cafeteria (bottom detaching at an intersection of duct work) and media (1 square foot cut out delaminating) outdoor air units have damaged exterior duct work insulation.