Indoor Environmental Quality HVAC Assessment of Glenelg High School: June 15th, 2021 (HXXGHS2021000048)

Assessor
Hummy Khan
Date
Outdoor Temperature
70°F
Relative Humidity
71%
Outdoor Dew Point
60°F

Air Handling Unit (Assess representative sample of RTU/AHU, including Portables)

Unit
Check OK Comments
Tag Number
Displayed
No
No tag numbers on several York, Venmar, McQuay brand rooftop units. No tag numbers on any exhaust fans either.
Status
Running
No
McQuay RTU-3 not running. Two McQuay rooftop units (no tag numbers) located front and right hand side of the building not running.
Outdoor Air Intake and Outdoor Air Dampers
Check OK Comments
Outdoor Pollution
Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
Yes
Louvers and Access Doors
Operating properly
Yes
Deflectors & Screens
Present
Yes
No debris
Yes
Dampers
Outside air damper: no obstructions
Yes
Return air damper: no obstructions
Yes
Mixing Plenum
Check OK Comments
Clean
No excess dirt, not used for storage
Yes
Insulation
Secure and Clean
Yes
P-Trap (if present)
Charged with liquid
Yes
Filters and Coils
Check OK Comments
Filters
Free of any bypassing
Yes
Correct size
Yes
Free from excessive loading, dampness or odor
Yes
Not collapsed/not fallen off
Yes
Present (not missing)
No
AHU-7 - Filter missing.
Date and initials written
No
York brand (no tag number) rooftop units and some McQuay brand rooftop units- No installation dates and name initials of the installing technician on filter.
Heating Coils
Clean, no noticeable leaks, or obstructions
Yes
Cooling Coils
Clean, no noticeable leaks, or obstructions
Yes
Access: Free of any obstructions in area that may affect access
Yes
Condensation: No excess condensation problems
Yes
Blowoff: Free of water from coil blowoff
Yes
Condensate Pan and Drain Line
No visible bacterial or fungal growth
Yes
Clean, no residue, no standing water
Yes
No Overflow, leakage, blockage, or damage
Yes
Proper slope, drain line ok, drainage acceptable, discharge okay
No
Multiple York and Venmar brand rooftop units (no tag numbers) and all (Munters brand) AHU-1, 2, 3 etc. rooftop units - Condensate drain improperly terminated, water dripping on roof from some units.
Fans and Motors
Check OK Comments
Condition
Operational
Yes
No unusual odors, noise, or vibration
Yes
Central Plant
Check OK Comments
Chilled Water Central Plant
Chiller operational
Yes
Heating Central Plant
Boiler operational
Yes
Misc. Comments
Work Order: 196762
Work Order Number(s)
196762
Issues found durring this assessment have been assigned to the above work order(s).