School
Assessor
Hummy Khan
Date
Outdoor Temperature
41°F
Relative Humidity
93%
Outdoor Dew Point
40°F
Air Handling Unit (Assess representative sample of RTU/AHU, including Portables)
Check | OK | Comments |
---|---|---|
Tag Number | ||
Displayed
|
Yes Work Order Closed by Building Maintenance
|
No tag number on one exhaust fan.
|
Status | ||
Running
|
Yes
|
Check | OK | Comments |
---|---|---|
Outdoor Pollution | ||
Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
|
Yes
|
|
Louvers and Access Doors | ||
Operating properly
|
Yes
|
|
Deflectors & Screens | ||
Present
|
Yes
|
|
No debris
|
Yes
|
|
Dampers | ||
Outside air damper: no obstructions
|
Yes Work Order Closed by Building Maintenance
|
Inconsistency on the position of the outside air dampers (OADs) from one unit to the other. On some units, the OADs appear to be 100% open and on others, 100% closed, while on others partially open. For example, AHU-1 and AHU-2, the OADs are 100% open, while on AHU-4 the are partially open. AHU-3 - The OADs are 100% closed.
|
Return air damper: no obstructions
|
Yes
|
Check | OK | Comments |
---|---|---|
Clean | ||
No excess dirt, not used for storage
|
Yes
|
|
Insulation | ||
Secure and Clean
|
Yes
|
|
P-Trap (if present) | ||
Charged with liquid
|
Yes
|
Check | OK | Comments |
---|---|---|
Filters | ||
Free of any bypassing
|
Yes
|
|
Correct size
|
Yes
|
|
Free from excessive loading, dampness or odor
|
Yes
|
|
Not collapsed/not fallen off
|
Yes
|
|
Present (not missing)
|
Yes
|
|
Date and initials written
|
Yes Work Order Closed by Building Maintenance
|
Rooftop Unit - 3 (RTU-3) - Filter dated July 2021. Should be replaced once a year per the HCPSS standard filter replacement schedule.
No initials on the filters of the installing technician on any units.
|
Heating Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Cooling Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Access: Free of any obstructions in area that may affect access
|
Yes
|
|
Condensation: No excess condensation problems
|
Yes
|
|
Blowoff: Free of water from coil blowoff
|
Yes
|
|
Condensate Pan and Drain Line | ||
No visible bacterial or fungal growth
|
Yes
|
|
Clean, no residue, no standing water
|
Yes
|
|
No Overflow, leakage, blockage, or damage
|
Yes
|
|
Proper slope, drain line ok, drainage acceptable, discharge okay
|
Yes Work Order Closed by Building Maintenance
|
Trane RTU-1 and RTU-2 - Condensate drain improperly terminated.
|
Check | OK | Comments |
---|---|---|
Condition | ||
Operational
|
Yes
|
|
No unusual odors, noise, or vibration
|
Yes Work Order Closed by Building Maintenance
|
Exhaust fan (no tag number, center of building) - Excessive noise.
|
Check | OK | Comments |
---|---|---|
Chilled Water Central Plant | ||
Chiller operational
|
Yes Work Order Closed by Building Maintenance
|
Chiller not operational - This has been reported to the HVAC Department. HVAC Department confirmed and reported they are working to get it repaired.
|
Cooling tower operational
|
Yes
|
Turned off for the heating season.
|
Heating Central Plant | ||
Boiler operational
|
Yes
|
Check | OK | Comments |
---|---|---|
Thermostat | ||
Thermostat setting acceptable
|
Yes Work Order Closed by Building Maintenance
|
Portable 218 and 219 - The system was set in "Heat" position. Changed to "Auto" position, while on site, which is the correct position.
|
Thermostat cover
|
Yes Work Order Closed by Building Maintenance
|
Portable 218 - Thermostat lock box loose at the wall mount and needs to properly re-anchored into the wall.
|
Fan Mode Correct
|
Yes Work Order Closed by Building Maintenance
|
Portable 218 - Fan was set in "On" position. Changed to "Auto" position, while on site, which is the proper position.
|
Space Temperature Acceptable
|
Yes
|
Misc. Comments
Automatic temperature control compressor in the mechanical room making excessive noise.
Work Order Number(s)
266005
Issues found durring this assessment have been assigned to the above
work order(s).