Assessor
Hummy Khan
Date
Outdoor Temperature
69°F
Relative Humidity
95%
Outdoor Dew Point
67°F
Air Handling Unit (Assess representative sample of RTU/AHU, including Portables)
Check | OK | Comments |
---|---|---|
Tag Number | ||
Displayed
|
Yes
|
|
Status | ||
Running
|
Yes
|
Check | OK | Comments |
---|---|---|
Outdoor Pollution | ||
Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
|
Yes
|
|
Louvers and Access Doors | ||
Operating properly
|
Yes
|
|
Deflectors & Screens | ||
Present
|
Yes
|
|
No debris
|
Yes
|
|
Dampers | ||
Outside air damper: no obstructions
|
Yes Work Order Closed by Building Maintenance
|
ACU-1 and ACU-2- Outside air dampers (OADs) appeared to be 100% closed.
|
Return air damper: no obstructions
|
Yes
|
Check | OK | Comments |
---|---|---|
Clean | ||
No excess dirt, not used for storage
|
Yes Work Order Closed by Building Maintenance
|
OAAHU-4 - Standing water in the mixing plenum.
Des Champ Unit - Intake hood dirty.
|
Insulation | ||
Secure and Clean
|
Yes
|
|
P-Trap (if present) | ||
Charged with liquid
|
Yes
|
Check | OK | Comments |
---|---|---|
Filters | ||
Free of any bypassing
|
Yes Work Order Closed by Building Maintenance
|
OAAHU-3- Air bypass between filters due to gap between filters.
OAAHU-4-Air bypass around filter because it's coming out from it's place.
|
Correct size
|
Yes
|
|
Free from excessive loading, dampness or odor
|
Yes Work Order Closed by Building Maintenance
|
OAAHU-1- Filters are wet and dirty and tree leaves are stuck on them. Also, the pressure gauge for the filters' pressure drop appears to be elevated.
OAAHU-2 and OAAHU-4 -The filters feel wet to the touch.
|
Not collapsed/not fallen off
|
Yes Work Order Closed by Building Maintenance
|
OAAHU-3 - Gap between the filters.
OAAHU-4 - Filter coming out from it's place due to improper placement and causing air bypass.
|
Present (not missing)
|
Yes Work Order Closed by Building Maintenance
|
OAAHU-2 - Second set of filters missing.
|
Date and initials written
|
Yes Work Order Closed by Building Maintenance
|
OAAHU-2, OAAHU-3, OAAHU-4, ACU-1, and ACU-2 - Filters dated July 2021, past due per HCPSS filter change program.
OAAHU-1- No installation date and name initials of the installing technician on the filters.
|
Heating Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Cooling Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Access: Free of any obstructions in area that may affect access
|
Yes
|
|
Condensation: No excess condensation problems
|
Yes
|
|
Blowoff: Free of water from coil blowoff
|
Yes
|
|
Condensate Pan and Drain Line | ||
No visible bacterial or fungal growth
|
Yes
|
|
Clean, no residue, no standing water
|
Yes
|
|
No Overflow, leakage, blockage, or damage
|
Yes
|
|
Proper slope, drain line ok, drainage acceptable, discharge okay
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Operational
|
Yes Work Order Closed by Building Maintenance
|
Exhaust Fan (EF)-4, EF-6 and EF-7 - Not running.
|
No unusual odors, noise, or vibration
|
Yes Work Order Closed by Building Maintenance
|
OAAHU-1 making a loud noise, repeat finding.
|
Check | OK | Comments |
---|---|---|
Chilled Water Central Plant | ||
Chiller operational
|
Yes
|
|
Cooling tower operational
|
Yes
|
|
Heating Central Plant | ||
Boiler operational
|
Yes
|
Check | OK | Comments |
---|---|---|
Thermostat | ||
Thermostat setting acceptable
|
Yes Work Order Closed by Building Maintenance
|
Portable #260- "Change air filter" alarm on thermostat screen display.
|
Thermostat cover
|
Yes
|
|
Fan Mode Correct
|
Yes
|
|
Space Temperature Acceptable
|
Yes
|
Work Order Number(s)
262281
Issues found durring this assessment have been assigned to the above
work order(s).