Assessor
Hummy Khan
Date
Outdoor Temperature
43°F
Relative Humidity
31%
Outdoor Dew Point
16°F
Air Handling Unit (Assess representative sample of RTU/AHU, including Portables)
Check | OK | Comments |
---|---|---|
Tag Number | ||
Displayed
|
No
|
No tag numbers on AAON rooftop units and several exhaust fans.
|
Status | ||
Running
|
Yes
|
Check | OK | Comments |
---|---|---|
Outdoor Pollution | ||
Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
|
Yes
|
|
Louvers and Access Doors | ||
Operating properly
|
Yes
|
|
Deflectors & Screens | ||
Present
|
Yes
|
|
No debris
|
Yes
|
|
Dampers | ||
Outside air damper: no obstructions
|
No
|
RAHU-1 Outside air dampers (OADs) appear to be closed. Two AAON units near OAAHU-2 OADs closed.
|
Return air damper: no obstructions
|
Yes
|
Check | OK | Comments |
---|---|---|
Clean | ||
No excess dirt, not used for storage
|
Yes
|
|
Insulation | ||
Secure and Clean
|
Yes
|
|
P-Trap (if present) | ||
Charged with liquid
|
Yes
|
Check | OK | Comments |
---|---|---|
Filters | ||
Free of any bypassing
|
No
|
OAAHU-1 and OAAHU-2 - Air bypass due to filters fallen off and/or bent.
|
Correct size
|
Yes
|
|
Free from excessive loading, dampness or odor
|
Yes
|
|
Not collapsed/not fallen off
|
No
|
OAAHU-1, OAAHU-2 and OAAHU-3 - Filters fallen off and bent. While on site managed to put two filters back on but unable to do the rest of them due to strong air pressure. The filter clips need to be properly installed for filters to stay in place.
|
Present (not missing)
|
No
|
AHU-2- Final filters missing.
|
Date and initials written
|
No
|
No initials on filters of installing technicians.
|
Heating Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Cooling Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Access: Free of any obstructions in area that may affect access
|
Yes
|
|
Condensation: No excess condensation problems
|
Yes
|
|
Blowoff: Free of water from coil blowoff
|
Yes
|
|
Condensate Pan and Drain Line | ||
No visible bacterial or fungal growth
|
Yes
|
|
Clean, no residue, no standing water
|
Yes
|
|
No Overflow, leakage, blockage, or damage
|
Yes
|
|
Proper slope, drain line ok, drainage acceptable, discharge okay
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Operational
|
No
|
Exhaust fans EF-8 and 9 - Not running may be for kitchen and controlled by a switch. EF near RAHU-1 not running.
|
No unusual odors, noise, or vibration
|
Yes
|
Check | OK | Comments |
---|---|---|
Chilled Water Central Plant | ||
Chiller operational
|
No
|
Not operational due to heating season.
|
Cooling tower operational
|
No
|
Not operational due to heating season.
|
Heating Central Plant | ||
Boiler operational
|
Yes
|
Check | OK | Comments |
---|---|---|
Thermostat | ||
Thermostat setting acceptable
|
No
|
Portable # 160 and 259- Maintaining occupied temperature set point while unoccupied.
|
Thermostat cover
|
Yes
|
|
Fan Mode Correct
|
Yes
|
|
Space Temperature Acceptable
|
Yes
|
Work Order Number(s)
180520
Issues found durring this assessment have been assigned to the above
work order(s).
Work Order: 180520