School
Assessor
Hummy Khan
Date
Outdoor Temperature
41°F
Relative Humidity
59%
Outdoor Dew Point
28°F
Air Handling Unit (Assess representative sample of RTU/AHU, including Portables)
Check | OK | Comments |
---|---|---|
Tag Number | ||
Displayed
|
No
|
Several exhaust fans have no tag numbers.
|
Status | ||
Running
|
No
|
RTU-1B and RTU-4 - Not operational. HVAC department contacted while onsite.
|
Check | OK | Comments |
---|---|---|
Outdoor Pollution | ||
Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
|
Yes
|
|
Louvers and Access Doors | ||
Operating properly
|
Yes
|
|
Deflectors & Screens | ||
Present
|
Yes
|
|
No debris
|
Yes
|
|
Dampers | ||
Outside air damper: no obstructions
|
No
|
AHU-1- Outside air dampers appear to be 100% open on a very cold day when they should only be partially open. Venmar RTU-2b-Outside air dampers appear to be closed.
|
Return air damper: no obstructions
|
No
|
AHU-1- Return air dampers appear to be closed when they should be open.
|
Check | OK | Comments |
---|---|---|
Clean | ||
No excess dirt, not used for storage
|
No
|
RTU-1A & 1B - Belts stored inside both units.
|
Insulation | ||
Secure and Clean
|
Yes
|
|
P-Trap (if present) | ||
Charged with liquid
|
Yes
|
Check | OK | Comments |
---|---|---|
Filters | ||
Free of any bypassing
|
Yes
|
|
Correct size
|
Yes
|
|
Free from excessive loading, dampness or odor
|
Yes
|
|
Not collapsed/not fallen off
|
Yes
|
|
Present (not missing)
|
No
|
AHU-1 and 2-Final filters missing.
|
Date and initials written
|
Yes
|
|
Heating Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Cooling Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Access: Free of any obstructions in area that may affect access
|
Yes
|
|
Condensation: No excess condensation problems
|
Yes
|
|
Blowoff: Free of water from coil blowoff
|
Yes
|
|
Condensate Pan and Drain Line | ||
No visible bacterial or fungal growth
|
Yes
|
|
Clean, no residue, no standing water
|
Yes
|
|
No Overflow, leakage, blockage, or damage
|
Yes
|
|
Proper slope, drain line ok, drainage acceptable, discharge okay
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Operational
|
No
|
Several exhaust fans not running. For example two exhaust fans near RTU-2A not running.
|
No unusual odors, noise, or vibration
|
No
|
EF-17 - Rattling.
|
Check | OK | Comments |
---|---|---|
Chilled Water Central Plant | ||
Chiller operational
|
Yes
|
Not operational due to heating season
|
Cooling tower operational
|
Yes
|
Not operational due to heating season
|
Heating Central Plant | ||
Boiler operational
|
Yes
|
Check | OK | Comments |
---|---|---|
Thermostat | ||
Thermostat setting acceptable
|
No
|
Portable 107- HVAC running in occupied mode while portable is unoccupied and maintaining occupied space temperature setting. Thermostat 107-2 display screen blank and unit not running. Thermostat 107-1 "Replace battery" message on display screen.
|
Thermostat cover
|
No
|
Portable 74-Thermostat cover missing.
|
Fan Mode Correct
|
Yes
|
|
Space Temperature Acceptable
|
Yes
|
Work Order Number(s)
178613
Issues found durring this assessment have been assigned to the above
work order(s).
2. RTU-4- Convenience electrical outlet security cover missing.
3. Filters improperly stored in mechanical penthouse.
Work Order: 178613