Indoor Environmental Quality HVAC Assessment of West Friendship Elementary School: March 31st, 2022 (HXWFES202200007C)

Assessor
Jeffrey Klenk
Date
Outdoor Temperature
69°F
Relative Humidity
71%
Outdoor Dew Point
59°F

Air Handling Unit (Assess representative sample of RTU/AHU, including Portables)

Unit
Check OK Comments
Tag Number
Displayed
Yes
Status
Running
Yes
Outdoor Air Intake and Outdoor Air Dampers
Check OK Comments
Outdoor Pollution
Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
Yes
Work Order Closed by Building Maintenance
AHU #5 - There is a sanitary vent near outdoor air intake.
Louvers and Access Doors
Operating properly
Yes
Work Order Closed by Building Maintenance
Gym - The louvers on the backside of the air return grille had heavy dust accumulation which may eventually impact airflow entering return.
Deflectors & Screens
Present
Yes
No debris
Yes
Dampers
Outside air damper: no obstructions
Yes
Work Order Closed by Building Maintenance
AHUs # 9 and 10 - Outdoor air dampers were closed. AHUs #6 and #7 - Outside air dampers were questionable as to being open.
Return air damper: no obstructions
Yes
Mixing Plenum
Check OK Comments
Clean
No excess dirt, not used for storage
Yes
Insulation
Secure and Clean
Yes
P-Trap (if present)
Charged with liquid
Yes
Filters and Coils
Check OK Comments
Filters
Free of any bypassing
Yes
Correct size
Yes
Free from excessive loading, dampness or odor
Yes
Not collapsed/not fallen off
Yes
Present (not missing)
Yes
Date and initials written
Yes
Heating Coils
Clean, no noticeable leaks, or obstructions
Yes
Work Order Closed by Building Maintenance
Gym AHU coil has particulate accumulation in some areas of the coil.
Cooling Coils
Clean, no noticeable leaks, or obstructions
Yes
Access: Free of any obstructions in area that may affect access
Yes
Condensation: No excess condensation problems
Yes
Blowoff: Free of water from coil blowoff
Yes
Condensate Pan and Drain Line
No visible bacterial or fungal growth
Yes
Clean, no residue, no standing water
Yes
No Overflow, leakage, blockage, or damage
Yes
Work Order Closed by Building Maintenance
AHU #2 - Exterior PVC condensate drain has some cracking causing a leak.
Proper slope, drain line ok, drainage acceptable, discharge okay
Yes
Fans and Motors
Check OK Comments
Condition
Operational
Yes
Work Order Closed by Building Maintenance
AHU #3 - Supply fan belt was off moving pulley. As a result, supply fan was not working.
No unusual odors, noise, or vibration
Yes
Central Plant
Check OK Comments
Heating Central Plant
Boiler operational
Yes
Work Order Number(s)
229813, 229814
Issues found durring this assessment have been assigned to the above work order(s).