Assessor
Hummy Khan
Date
Outdoor Temperature
46°F
Relative Humidity
42%
Outdoor Dew Point
25°F
Air Handling Unit (Assess representative sample of RTU/AHU, including Portables)
Check | OK | Comments |
---|---|---|
Tag Number | ||
Displayed
|
No
|
All exhaust fans on the roof above mechanical room do not have tag numbers. Also, exhaust fans near AHU-6 (AAON unit) and near AHU-2 (Deschamp unit) do not have tag numbers.
|
Status | ||
Running
|
Yes
|
Check | OK | Comments |
---|---|---|
Outdoor Pollution | ||
Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
|
Yes
|
|
Louvers and Access Doors | ||
Operating properly
|
Yes
|
|
Deflectors & Screens | ||
Present
|
Yes
|
|
No debris
|
Yes
|
|
Dampers | ||
Outside air damper: no obstructions
|
No
|
AAON AHU-8 and 9 - Outside air dampers appeared to be 100% closed.
|
Return air damper: no obstructions
|
Yes
|
Check | OK | Comments |
---|---|---|
Clean | ||
No excess dirt, not used for storage
|
No
|
AHU-5 - Filter access door needs cleaning.
|
Insulation | ||
Secure and Clean
|
Yes
|
|
P-Trap (if present) | ||
Charged with liquid
|
Yes
|
Check | OK | Comments |
---|---|---|
Filters | ||
Free of any bypassing
|
Yes
|
|
Correct size
|
Yes
|
|
Free from excessive loading, dampness or odor
|
No
|
AHU-5 - Pressure gauge not working.
|
Not collapsed/not fallen off
|
Yes
|
|
Present (not missing)
|
Yes
|
|
Date and initials written
|
No
|
Initials are missing from all filters.
|
Heating Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Cooling Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Access: Free of any obstructions in area that may affect access
|
Yes
|
|
Condensation: No excess condensation problems
|
Yes
|
|
Blowoff: Free of water from coil blowoff
|
Yes
|
|
Condensate Pan and Drain Line | ||
No visible bacterial or fungal growth
|
Yes
|
|
Clean, no residue, no standing water
|
Yes
|
|
No Overflow, leakage, blockage, or damage
|
Yes
|
|
Proper slope, drain line ok, drainage acceptable, discharge okay
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Operational
|
No
|
Exhaust fan (no tag #) near AHU-6 and four exhaust fans (no tag #) on the roof above mechanical room - Not operational.
|
No unusual odors, noise, or vibration
|
No
|
Exhaust Fan-8 and exhaust fan (no tag #) near AHU-2 (Deschamp) - Rattling. Deschamp AHU-1 supply fan appears to be making loud noise.
|
Check | OK | Comments |
---|---|---|
Chilled Water Central Plant | ||
Chiller operational
|
No
|
Not operational due to heating season
|
Cooling tower operational
|
Yes
|
Not operational due to heating season
|
Heating Central Plant | ||
Boiler operational
|
Yes
|
Work Order Number(s)
177669
Issues found durring this assessment have been assigned to the above
work order(s).
Work Order: 177669