Assessor
Hummy Khan
Date
Outdoor Temperature
39°F
Relative Humidity
45%
Outdoor Dew Point
21°F
Air Handling Unit (Assess representative sample of RTU/AHU, including Portables)
Check | OK | Comments |
---|---|---|
Tag Number | ||
Displayed
|
No
|
Several Exhaust Fans- No tag numbers. Also, no tag number on one RTU (handwritten Kindergarten).
|
Status | ||
Running
|
No
|
AHU-3 - Not running. Informed the HVAC department about this by text while on site.
|
Check | OK | Comments |
---|---|---|
Outdoor Pollution | ||
Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
|
Yes
|
|
Louvers and Access Doors | ||
Operating properly
|
Yes
|
|
Deflectors & Screens | ||
Present
|
Yes
|
|
No debris
|
Yes
|
|
Dampers | ||
Outside air damper: no obstructions
|
No
|
AHU-1, 4, 5, 7, 8 and Kindergarten Unit - Outside air dampers 100% closed. AHU-6 - Outside air dampers barely open.
|
Return air damper: no obstructions
|
Yes
|
Check | OK | Comments |
---|---|---|
Clean | ||
No excess dirt, not used for storage
|
Yes
|
|
Insulation | ||
Secure and Clean
|
Yes
|
|
P-Trap (if present) | ||
Charged with liquid
|
Yes
|
Check | OK | Comments |
---|---|---|
Filters | ||
Free of any bypassing
|
No
|
AHU-3, 4, 7 - Air bypass around filters due to incorrect size.
|
Correct size
|
No
|
AHU-3, 4, 7 - Incorrect filter size.
|
Free from excessive loading, dampness or odor
|
Yes
|
|
Not collapsed/not fallen off
|
Yes
|
|
Present (not missing)
|
Yes
|
|
Date and initials written
|
No
|
No technician's initials on any filters.
|
Heating Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Cooling Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Access: Free of any obstructions in area that may affect access
|
Yes
|
|
Condensation: No excess condensation problems
|
Yes
|
|
Blowoff: Free of water from coil blowoff
|
Yes
|
|
Condensate Pan and Drain Line | ||
No visible bacterial or fungal growth
|
Yes
|
|
Clean, no residue, no standing water
|
Yes
|
|
No Overflow, leakage, blockage, or damage
|
Yes
|
|
Proper slope, drain line ok, drainage acceptable, discharge okay
|
No
|
Condensate drain on all units except (AHU for Kindergarten) improperly terminated.
|
Check | OK | Comments |
---|---|---|
Condition | ||
Operational
|
No
|
Several exhaust fans not running. One exhaust near AHU-7 and at least three exhaust fans on the same roof as AHU-8 are not operational.
|
No unusual odors, noise, or vibration
|
Yes
|
Check | OK | Comments |
---|---|---|
Chilled Water Central Plant | ||
Chiller operational
|
Yes
|
|
Heating Central Plant | ||
Boiler operational
|
Yes
|
Misc. Comments
Work Order: 178157
Work Order Number(s)
178157
Issues found durring this assessment have been assigned to the above
work order(s).