Assessor
Hummy Khan
Date
Outdoor Temperature
66°F
Relative Humidity
79%
Outdoor Dew Point
61°F
Air Handling Unit (Assess representative sample of RTU/AHU, including Portables)
Check | OK | Comments |
---|---|---|
Tag Number | ||
Displayed
|
No
|
Some of the exhaust fans do not appear to have tag numbers on them. For instance two exhaust fans near ACU-6.
|
Status | ||
Running
|
No
|
Hasting RTU for the Gym - Not operating and partially covered with tarp.
|
Check | OK | Comments |
---|---|---|
Outdoor Pollution | ||
Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
|
No
|
|
Louvers and Access Doors | ||
Operating properly
|
No
|
ACU-6 - Access door latch appears to be broken and is not completely latched.
|
Deflectors & Screens | ||
Present
|
Yes
|
|
No debris
|
Yes
|
|
Dampers | ||
Outside air damper: no obstructions
|
No
|
ACU-5 and ACU-6 - Outside air dampers are completely closed.
|
Return air damper: no obstructions
|
No
|
ACU-2 - Return air dampers are closed while OADs are open.
|
Check | OK | Comments |
---|---|---|
Clean | ||
No excess dirt, not used for storage
|
Yes
|
|
Insulation | ||
Secure and Clean
|
Yes
|
|
P-Trap (if present) | ||
Charged with liquid
|
Yes
|
Check | OK | Comments |
---|---|---|
Filters | ||
Free of any bypassing
|
Yes
|
|
Correct size
|
Yes
|
|
Free from excessive loading, dampness or odor
|
Yes
|
|
Not collapsed/not fallen off
|
Yes
|
|
Present (not missing)
|
Yes
|
|
Date and initials written
|
Yes
|
|
Heating Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Cooling Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Access: Free of any obstructions in area that may affect access
|
Yes
|
|
Condensation: No excess condensation problems
|
Yes
|
|
Blowoff: Free of water from coil blowoff
|
Yes
|
|
Condensate Pan and Drain Line | ||
No visible bacterial or fungal growth
|
Yes
|
|
Clean, no residue, no standing water
|
Yes
|
|
No Overflow, leakage, blockage, or damage
|
No
|
ACU-1 - Condensate drain line leaking.
|
Proper slope, drain line ok, drainage acceptable, discharge okay
|
No
|
Check | OK | Comments |
---|---|---|
Condition | ||
Operational
|
No
|
ACU-1, ACU-3, ACU-6, and ACU-7 - Relief fan not running. Exhaust Fan for the Gym - Not running. Two exhaust fans near ACU-6 and one exhaust fan near ACU-1 do not appear to be running.
|
No unusual odors, noise, or vibration
|
No
|
ACU-1 - Supply fan making noise.
|
Check | OK | Comments |
---|---|---|
Heating Central Plant | ||
Boiler operational
|
Yes
|
Check | OK | Comments |
---|---|---|
Thermostat | ||
Thermostat setting acceptable
|
Yes
|
|
Thermostat cover
|
No
|
Portable 213 - Stat cover on, but not locked.
|
Fan Mode Correct
|
Yes
|
|
Space Temperature Acceptable
|
Yes
|
Misc. Comments
Work Order: 171898
Work Order Number(s)
171898
Issues found durring this assessment have been assigned to the above
work order(s).