Assessor
Hummy Khan
Date
Outdoor Temperature
47°F
Relative Humidity
73%
Outdoor Dew Point
39°F
Air Handling Unit (Assess representative sample of RTU/AHU, including Portables)
Check | OK | Comments |
---|---|---|
Tag Number | ||
Displayed
|
Yes Work Order Closed by Building Maintenance
|
No tag numbers on any exhaust fans.
|
Status | ||
Running
|
Yes
|
Check | OK | Comments |
---|---|---|
Outdoor Pollution | ||
Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
|
Yes
|
|
Louvers and Access Doors | ||
Operating properly
|
Yes
|
|
Deflectors & Screens | ||
Present
|
Yes
|
|
No debris
|
Yes
|
|
Dampers | ||
Outside air damper: no obstructions
|
Yes Work Order Closed by Building Maintenance
|
Inconsistency on the position of outside air dampers (OADs) from one unit to the other. On some units OADs appear to be 100% open and on others closed.
|
Return air damper: no obstructions
|
Yes Work Order Closed by Building Maintenance
|
Similarly, there is inconsistency on the position of return air dampers (RADs) from one unit to the other. On some units return air dampers appear to be 100% open and on others, 100% closed.
|
Check | OK | Comments |
---|---|---|
Clean | ||
No excess dirt, not used for storage
|
Yes
|
|
Insulation | ||
Secure and Clean
|
Yes
|
|
P-Trap (if present) | ||
Charged with liquid
|
Yes
|
Check | OK | Comments |
---|---|---|
Filters | ||
Free of any bypassing
|
Yes
|
|
Correct size
|
Yes
|
|
Free from excessive loading, dampness or odor
|
Yes
|
|
Not collapsed/not fallen off
|
Yes
|
|
Present (not missing)
|
Yes
|
|
Date and initials written
|
Yes
|
|
Heating Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Cooling Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Access: Free of any obstructions in area that may affect access
|
Yes
|
|
Condensation: No excess condensation problems
|
Yes
|
|
Blowoff: Free of water from coil blowoff
|
Yes
|
|
Condensate Pan and Drain Line | ||
No visible bacterial or fungal growth
|
Yes
|
|
Clean, no residue, no standing water
|
Yes
|
|
No Overflow, leakage, blockage, or damage
|
Yes
|
|
Proper slope, drain line ok, drainage acceptable, discharge okay
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Operational
|
Yes
|
|
No unusual odors, noise, or vibration
|
Yes
|
Check | OK | Comments |
---|---|---|
Heating Central Plant | ||
Boiler operational
|
Yes
|
Check | OK | Comments |
---|---|---|
Thermostat | ||
Thermostat setting acceptable
|
Yes Work Order Closed by Building Maintenance
|
Portable #103- Per the thermostat screen display, system in emergency heat mode, not sure why and the space temperature 64 deg. System should be assessed.
|
Thermostat cover
|
Yes Work Order Closed by Building Maintenance
|
Portable # 105- Thermostat front cover missing.
|
Fan Mode Correct
|
Yes
|
|
Space Temperature Acceptable
|
Yes
|
Misc. Comments
It appears that the mechanical cooling is running on several units at 47 deg. outside temperature. If cooling is needed, economizer mode should be working to bring in cooler outside air up to 100% to cool the spaces. This mode will provide better indoor environment quality (IEQ) and at the same time save tremendous amount of energy and cost and will extend the life of certain portions of the units. Highly recommend checking and verifying the operation of the economizer mode and other controls operation in the field.
Work Order Number(s)
216672
Issues found durring this assessment have been assigned to the above
work order(s).