School
              
          Assessor
          Hummy Khan
        Date
              Outdoor Temperature
              48°F
          Relative Humidity
              47%
          Outdoor Dew Point
              28°F
          Air Handling Unit (Assess representative sample of RTU/AHU, including Portables)
| Check | OK | Comments | 
|---|---|---|
| Tag Number | ||
| 
        Displayed
         | Yes Work Order Closed by Building Maintenance | 
        No tag numbers on any exhaust fans.
         | 
| Status | ||
| 
        Running
         | Yes Work Order Closed by Building Maintenance | 
        Air Handling Unit-4 - Not running. 
         | 
| Check | OK | Comments | 
|---|---|---|
| Outdoor Pollution | ||
| 
        Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
         | Yes | |
| Louvers and Access Doors | ||
| 
        Operating properly
         | Yes | |
| Deflectors & Screens | ||
| 
        Present
         | Yes | |
| 
        No debris
         | Yes | |
| Dampers | ||
| 
        Outside air damper: no obstructions
         | Yes Work Order Closed by Building Maintenance | 
        AHU-2, AHU-11 and AHU-19 - Outside air dampers (OADs) are closed. 
AHU-5 - OADs are insignificantly open. 
         | 
| 
        Return air damper: no obstructions
         | Yes | |
| Check | OK | Comments | 
|---|---|---|
| Clean | ||
| 
        No excess dirt, not used for storage
         | Yes | |
| Insulation | ||
| 
        Secure and Clean
         | Yes | |
| P-Trap (if present) | ||
| 
        Charged with liquid
         | Yes | |
| Check | OK | Comments | 
|---|---|---|
| Filters | ||
| 
        Free of any bypassing
         | Yes Work Order Closed by Building Maintenance | 
        AHU-5, AHU-6, AHU-9, AHU-14, AHU-16 - Air bypass around filters.
         | 
| 
        Correct size
         | Yes | |
| 
        Free from excessive loading, dampness or odor
         | Yes | |
| 
        Not collapsed/not fallen off
         | Yes | |
| 
        Present (not missing)
         | Yes | |
| 
        Date and initials written
         | Yes Work Order Closed by Building Maintenance | 
        AHU-6 and AHU-9 -  No initials of the technician installing filters.
         | 
| Heating Coils | ||
| 
        Clean, no noticeable leaks, or obstructions
         | Yes | |
| Cooling Coils | ||
| 
        Clean, no noticeable leaks, or obstructions
         | Yes | |
| 
        Access: Free of any obstructions in area that may affect access
         | Yes | |
| 
        Condensation: No excess condensation problems
         | Yes | |
| 
        Blowoff: Free of water from coil blowoff
         | Yes | |
| Condensate Pan and Drain Line | ||
| 
        No visible bacterial or fungal growth
         | Yes | |
| 
        Clean, no residue, no standing water
         | Yes | |
| 
        No Overflow, leakage, blockage, or damage
         | Yes | |
| 
        Proper slope, drain line ok, drainage acceptable, discharge okay
         | Yes | |
| Check | OK | Comments | 
|---|---|---|
| Condition | ||
| 
        Operational
         | Yes Work Order Closed by Building Maintenance | 
        Several exhaust fans (no tag number) - Not operating.  
         | 
| 
        No unusual odors, noise, or vibration
         | Yes | |
| Check | OK | Comments | 
|---|---|---|
| Chilled Water Central Plant | ||
| 
        Chiller operational
         | Yes Work Order Closed by Building Maintenance | 
        Turned off due to heating season. 
         | 
| 
        Cooling tower operational
         | Yes Work Order Closed by Building Maintenance | 
        Turned off due to heating season. 
         | 
| Heating Central Plant | ||
| 
        Boiler operational
         | Yes | |
Misc. Comments
              Brand new air filters laying open on the floor between AHU-9 and AHU-10. 
          Work Order Number(s)
                     220425   
      
          
        Issues found durring this assessment have been assigned to the above
        work order(s).
      
    