Assessor
Hummy Khan
Date
Outdoor Temperature
48°F
Relative Humidity
37%
Outdoor Dew Point
24°F
Air Handling Unit (Assess representative sample of RTU/AHU, including Portables)
Check | OK | Comments |
---|---|---|
Tag Number | ||
Displayed
|
Yes
|
|
Status | ||
Running
|
Yes Work Order Closed by Building Maintenance
|
Rooftop Unit (RTU) - 11 - Not running. Turned off at the switch on the unit.
|
Check | OK | Comments |
---|---|---|
Outdoor Pollution | ||
Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
|
Yes
|
|
Louvers and Access Doors | ||
Operating properly
|
Yes
|
|
Deflectors & Screens | ||
Present
|
Yes
|
|
No debris
|
Yes
|
|
Dampers | ||
Outside air damper: no obstructions
|
Yes Work Order Closed by Building Maintenance
|
Inconsistency on the position of the outside air dampers (OADs) from one unit to the other. On some units, OADs appear to be 100% open and on others partially open.
RTU-2, RTU-3, RTU-4, RTU-5, RTU-6, RTU-7 and RTU-10 - OADs are 100% open. At the time of walkthrough, the outside temperature was 48 degrees Fahrenheit (F). The OADs should not be 100% open at that temperature.
|
Return air damper: no obstructions
|
Yes Work Order Closed by Building Maintenance
|
Inconsistency on the position of the Return Air Dampers (RADs) from one unit to the other. On some units RADs appear to be 100% closed and on others partially open. For example, RTU-2, 4 and RTU-10- Eeturn air dampers (RAD) 100% closed and other units partially open.
|
Check | OK | Comments |
---|---|---|
Clean | ||
No excess dirt, not used for storage
|
Yes
|
|
Insulation | ||
Secure and Clean
|
Yes
|
|
P-Trap (if present) | ||
Charged with liquid
|
Yes
|
Check | OK | Comments |
---|---|---|
Filters | ||
Free of any bypassing
|
Yes
|
|
Correct size
|
Yes
|
|
Free from excessive loading, dampness or odor
|
Yes
|
|
Not collapsed/not fallen off
|
Yes
|
|
Present (not missing)
|
Yes
|
|
Date and initials written
|
Yes Work Order Closed by Building Maintenance
|
No initials of the installing technician on filters.
|
Heating Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Cooling Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Access: Free of any obstructions in area that may affect access
|
Yes
|
|
Condensation: No excess condensation problems
|
Yes
|
|
Blowoff: Free of water from coil blowoff
|
Yes
|
|
Condensate Pan and Drain Line | ||
No visible bacterial or fungal growth
|
Yes
|
|
Clean, no residue, no standing water
|
Yes
|
|
No Overflow, leakage, blockage, or damage
|
Yes
|
|
Proper slope, drain line ok, drainage acceptable, discharge okay
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Operational
|
Yes
|
|
No unusual odors, noise, or vibration
|
Yes
|
Check | OK | Comments |
---|---|---|
Chilled Water Central Plant | ||
Chiller operational
|
Yes
|
|
Heating Central Plant | ||
Boiler operational
|
Yes
|
Check | OK | Comments |
---|---|---|
Thermostat | ||
Thermostat setting acceptable
|
Yes Work Order Closed by Building Maintenance
|
Portable-134- Thermostat in alarm "Change air filter" message on the display screen.
Portable135- Heat set at 66 degrees F, below the HCPSS standard of 70 degrees F.
|
Thermostat cover
|
Yes Work Order Closed by Building Maintenance
|
Portable-135- Thermostat lock box was not locked, locked it while on site.
|
Fan Mode Correct
|
Yes
|
|
Space Temperature Acceptable
|
Yes
|
Work Order Number(s)
265082
Issues found durring this assessment have been assigned to the above
work order(s).