Assessor
Hummy Khan
Date
Outdoor Temperature
48°F
Relative Humidity
79%
Outdoor Dew Point
41°F
Air Handling Unit (Assess representative sample of RTU/AHU, including Portables)
Check | OK | Comments |
---|---|---|
Tag Number | ||
Displayed
|
Yes
|
|
Status | ||
Running
|
Yes
|
Check | OK | Comments |
---|---|---|
Outdoor Pollution | ||
Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
|
Yes
|
|
Louvers and Access Doors | ||
Operating properly
|
Yes
|
|
Deflectors & Screens | ||
Present
|
Yes
|
|
No debris
|
Yes
|
|
Dampers | ||
Outside air damper: no obstructions
|
No
|
McQuay RTU (only one unit without a tag number) - Outside air dampers 100% closed. RTU-8 outside air dampers barely open compared to the other units.
|
Return air damper: no obstructions
|
Yes
|
Check | OK | Comments |
---|---|---|
Clean | ||
No excess dirt, not used for storage
|
Yes
|
|
Insulation | ||
Secure and Clean
|
Yes
|
|
P-Trap (if present) | ||
Charged with liquid
|
Yes
|
Check | OK | Comments |
---|---|---|
Filters | ||
Free of any bypassing
|
No
|
McQuay RTU (only one McQuay unit, no tag #) - Air bypass around filters.
|
Correct size
|
Yes
|
|
Free from excessive loading, dampness or odor
|
Yes
|
|
Not collapsed/not fallen off
|
No
|
RTU-10 - One filter was installed backwards but was corrected during inspection.
|
Present (not missing)
|
No
|
RTU-12 - A few pre-filters missing, but no bypass.
|
Date and initials written
|
Yes
|
|
Heating Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Cooling Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Access: Free of any obstructions in area that may affect access
|
Yes
|
|
Condensation: No excess condensation problems
|
Yes
|
|
Blowoff: Free of water from coil blowoff
|
Yes
|
|
Condensate Pan and Drain Line | ||
No visible bacterial or fungal growth
|
Yes
|
|
Clean, no residue, no standing water
|
Yes
|
|
No Overflow, leakage, blockage, or damage
|
Yes
|
|
Proper slope, drain line ok, drainage acceptable, discharge okay
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Operational
|
Yes
|
|
No unusual odors, noise, or vibration
|
Yes
|
Check | OK | Comments |
---|---|---|
Heating Central Plant | ||
Boiler operational
|
Yes
|
Check | OK | Comments |
---|---|---|
Thermostat | ||
Thermostat setting acceptable
|
No
|
Portable #263 and #264 - Stat in air conditioning mode and all the settings appear to be off. Portable #135 thermostat on "Permanent Hold".
|
Thermostat cover
|
No
|
Portable #263 and #264 - No cover.
|
Fan Mode Correct
|
Yes
|
|
Space Temperature Acceptable
|
No
|
Portable #263 and #264 -56 deg space temperature. Portable #134 recorded 93 deg space temperature on the fluke. Thermostat display showed "Auxiliary Heat On" Building Maintenance was notified and responded promptly.
|
Work Order Number(s)
172832
Issues found durring this assessment have been assigned to the above
work order(s).
Work Order: 172832