Indoor Environmental Quality HVAC Assessment of Oakland Mills High School: February 2nd, 2024 (HXOMHS20240000EE)

Assessor
Hummy Khan
Date
Outdoor Temperature
45°F
Relative Humidity
84%
Outdoor Dew Point
40°F

Air Handling Unit (Assess representative sample of RTU/AHU, including Portables)

Unit
Check OK Comments
Tag Number
Displayed
No
No tag numbers on any exhaust fans, repeat finding.
Status
Running
Yes
Outdoor Air Intake and Outdoor Air Dampers
Check OK Comments
Outdoor Pollution
Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
Yes
Louvers and Access Doors
Operating properly
Yes
Deflectors & Screens
Present
Yes
No debris
Yes
Dampers
Outside air damper: no obstructions
No
RTU-8 (Trane) - Outside air dampers (OADs) appeared to be 100% closed.
Return air damper: no obstructions
Yes
Mixing Plenum
Check OK Comments
Clean
No excess dirt, not used for storage
Yes
Insulation
Secure and Clean
Yes
P-Trap (if present)
Charged with liquid
Yes
Filters and Coils
Check OK Comments
Filters
Free of any bypassing
No
RTU-9- Even with bypass plate there is air bypass. Install correct size filters or correct size bypass plate to prevent air bypass.
Correct size
No
RTU-9- Incorrect size filters installed requiring bypass plate to be installed to prevent air bypass. The plate is an improper size and is loose and falling off.
Free from excessive loading, dampness or odor
No
AHU-8- Filters appeared to be excessively dirty.
Not collapsed/not fallen off
Yes
Present (not missing)
Yes
Date and initials written
Yes
Heating Coils
Clean, no noticeable leaks, or obstructions
Yes
Cooling Coils
Clean, no noticeable leaks, or obstructions
Yes
Access: Free of any obstructions in area that may affect access
Yes
Condensation: No excess condensation problems
Yes
Blowoff: Free of water from coil blowoff
Yes
Condensate Pan and Drain Line
No visible bacterial or fungal growth
Yes
Clean, no residue, no standing water
Yes
No Overflow, leakage, blockage, or damage
Yes
Proper slope, drain line ok, drainage acceptable, discharge okay
No
RTU-2- Broken condensate drain line. RTU-3 (McQuay) and RTU-7 (AAON)- Condensate drain improperly terminated, repeat finding.
Fans and Motors
Check OK Comments
Condition
Operational
Yes
No unusual odors, noise, or vibration
Yes
Central Plant
Check OK Comments
Chilled Water Central Plant
Chiller operational
Yes
Turned off for the heating season.
Cooling tower operational
Yes
Turned off for the heating season.
Heating Central Plant
Boiler operational
Yes
Misc. Comments
The door to the small mechanical penthouse near the front of the building was open. Closed while on site.
Work Order Number(s)
11278
Issues found durring this assessment have been assigned to the above work order(s).