School
Assessor
Hummy Khan
Date
Outdoor Temperature
57°F
Relative Humidity
85%
Outdoor Dew Point
52°F
Air Handling Unit (Assess representative sample of RTU/AHU, including Portables)
Check | OK | Comments |
---|---|---|
Tag Number | ||
Displayed
|
No
|
None of the exhaust fans have tag numbers on them.
|
Status | ||
Running
|
Yes
|
.
|
Check | OK | Comments |
---|---|---|
Outdoor Pollution | ||
Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
|
Yes
|
|
Louvers and Access Doors | ||
Operating properly
|
Yes
|
|
Deflectors & Screens | ||
Present
|
Yes
|
|
No debris
|
Yes
|
|
Dampers | ||
Outside air damper: no obstructions
|
No
|
AAON-RTU-7, Trane RTU-9, 10, and 11- Outside air dampers appear to be 100 % closed.
|
Return air damper: no obstructions
|
No
|
Trane AHU-8 return air dampers appear to be 100% closed while outside air dampers appear to be 100% open.
|
Check | OK | Comments |
---|---|---|
Clean | ||
No excess dirt, not used for storage
|
Yes
|
|
Insulation | ||
Secure and Clean
|
Yes
|
|
P-Trap (if present) | ||
Charged with liquid
|
Yes
|
Check | OK | Comments |
---|---|---|
Filters | ||
Free of any bypassing
|
No
|
AHU-5, RTU-9, 10, 11 - Air bypass around filter(s).
|
Correct size
|
No
|
AHU-5, RTU-9, 10 and 11 - Appear to be incorrect size.
|
Free from excessive loading, dampness or odor
|
Yes
|
|
Not collapsed/not fallen off
|
Yes
|
|
Present (not missing)
|
Yes
|
|
Date and initials written
|
Yes
|
|
Heating Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Cooling Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Access: Free of any obstructions in area that may affect access
|
Yes
|
|
Condensation: No excess condensation problems
|
Yes
|
|
Blowoff: Free of water from coil blowoff
|
Yes
|
|
Condensate Pan and Drain Line | ||
No visible bacterial or fungal growth
|
Yes
|
|
Clean, no residue, no standing water
|
Yes
|
|
No Overflow, leakage, blockage, or damage
|
Yes
|
|
Proper slope, drain line ok, drainage acceptable, discharge okay
|
No
|
RTU-3 - Drain improperly terminated.
|
Check | OK | Comments |
---|---|---|
Condition | ||
Operational
|
No
|
Hood missing from exhaust fan in the science room addition part of the roof.
|
No unusual odors, noise, or vibration
|
Yes
|
Check | OK | Comments |
---|---|---|
Chilled Water Central Plant | ||
Chiller operational
|
No
|
Not running due to winter mode.
|
Cooling tower operational
|
No
|
Not running due to winter mode.
|
Heating Central Plant | ||
Boiler operational
|
Yes
|
Work Order Number(s)
169818
Issues found durring this assessment have been assigned to the above
work order(s).
Work Order: 169818