Indoor Environmental Quality HVAC Assessment of Manor Woods Elementary School: March 30th, 2021 (HXMWES202100003F)

Assessor
Hummy Khan
Date
Outdoor Temperature
68°F
Relative Humidity
31%
Outdoor Dew Point
37°F

Air Handling Unit (Assess representative sample of RTU/AHU, including Portables)

Unit
Check OK Comments
Tag Number
Displayed
Yes
Status
Running
No
RTU-1 not running. Informed the HVAC department of this while on site.
Outdoor Air Intake and Outdoor Air Dampers
Check OK Comments
Outdoor Pollution
Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
Yes
Louvers and Access Doors
Operating properly
Yes
Deflectors & Screens
Present
Yes
No debris
Yes
Dampers
Outside air damper: no obstructions
Yes
Return air damper: no obstructions
Yes
Mixing Plenum
Check OK Comments
Clean
No excess dirt, not used for storage
No
RTU-10 - Mixing section very dirty.
Insulation
Secure and Clean
Yes
P-Trap (if present)
Charged with liquid
Yes
Filters and Coils
Check OK Comments
Filters
Free of any bypassing
No
RTU-10- Air bypass around filters.
Correct size
Yes
Free from excessive loading, dampness or odor
Yes
Not collapsed/not fallen off
No
RTU-2-Filters collapsed.
Present (not missing)
Yes
Date and initials written
Yes
Heating Coils
Clean, no noticeable leaks, or obstructions
Yes
Cooling Coils
Clean, no noticeable leaks, or obstructions
Yes
Access: Free of any obstructions in area that may affect access
Yes
Condensation: No excess condensation problems
Yes
Blowoff: Free of water from coil blowoff
Yes
Condensate Pan and Drain Line
No visible bacterial or fungal growth
Yes
Clean, no residue, no standing water
Yes
No Overflow, leakage, blockage, or damage
Yes
Proper slope, drain line ok, drainage acceptable, discharge okay
No
Condensate drain on all rooftop units improperly terminated.
Fans and Motors
Check OK Comments
Condition
Operational
No
Exhaust Fan-12 - Not running.
No unusual odors, noise, or vibration
Yes
Central Plant
Check OK Comments
Heating Central Plant
Boiler operational
Yes
Misc. Comments
Two refrigerant cylinders laying on the roof next to Gym rooftop unit RTU-10.

Work Order: 187736
Work Order Number(s)
187736
Issues found durring this assessment have been assigned to the above work order(s).