School
Assessor
Hummy Khan
Date
Outdoor Temperature
54°F
Relative Humidity
44%
Outdoor Dew Point
32°F
Air Handling Unit (Assess representative sample of RTU/AHU, including Portables)
Check | OK | Comments |
---|---|---|
Tag Number | ||
Displayed
|
No
|
A few exhaust fans do not have tag numbers.
|
Status | ||
Running
|
Yes
|
Check | OK | Comments |
---|---|---|
Outdoor Pollution | ||
Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
|
Yes
|
|
Louvers and Access Doors | ||
Operating properly
|
Yes
|
|
Deflectors & Screens | ||
Present
|
Yes
|
|
No debris
|
Yes
|
|
Dampers | ||
Outside air damper: no obstructions
|
No
|
RTU-3 - Outside air dampers are not as opened as other units.
|
Return air damper: no obstructions
|
Yes
|
Check | OK | Comments |
---|---|---|
Clean | ||
No excess dirt, not used for storage
|
Yes
|
|
Insulation | ||
Secure and Clean
|
Yes
|
|
P-Trap (if present) | ||
Charged with liquid
|
Yes
|
Check | OK | Comments |
---|---|---|
Filters | ||
Free of any bypassing
|
No
|
RTU-1, 2, 3, 6 - Air bypass due to incorrect size filters.
|
Correct size
|
No
|
Several rooftop units for example RTU-1, 2, 3, 4 and 6 - Incorrect size filters. In RTU-4, filters getting bent due to incorrect size.
|
Free from excessive loading, dampness or odor
|
Yes
|
|
Not collapsed/not fallen off
|
Yes
|
|
Present (not missing)
|
Yes
|
|
Date and initials written
|
No
|
RTU-6- No date on filters.
|
Heating Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Cooling Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Access: Free of any obstructions in area that may affect access
|
Yes
|
|
Condensation: No excess condensation problems
|
Yes
|
|
Blowoff: Free of water from coil blowoff
|
Yes
|
|
Condensate Pan and Drain Line | ||
No visible bacterial or fungal growth
|
Yes
|
|
Clean, no residue, no standing water
|
Yes
|
|
No Overflow, leakage, blockage, or damage
|
Yes
|
|
Proper slope, drain line ok, drainage acceptable, discharge okay
|
No
|
All units - Condensate drain improperly terminated.
|
Check | OK | Comments |
---|---|---|
Condition | ||
Operational
|
No
|
Few exhaust fans near the kitchen H&V unit not running. Exhaust fan- F-13 not running. Exhaust fan near RTU-1 not running.
|
No unusual odors, noise, or vibration
|
No
|
RTU-4- Return/relief fan noisy. Also RTU-2 noisy.
|
Check | OK | Comments |
---|---|---|
Heating Central Plant | ||
Boiler operational
|
Yes
|
Check | OK | Comments |
---|---|---|
Thermostat | ||
Thermostat setting acceptable
|
No
|
Portable #146- Appears, no motion sensor installed. Portable #166- Auxiliary heat came on instead of regular with only 54 deg. outside temperature. Also, thermostat cover guard not properly closed but was taken care of at the time of inspection. Portable # 144- No motion sensor installed. Portable #60 maintaining 70 deg space temperature despite the motion sensor installed and no one present.
|
Thermostat cover
|
Yes
|
|
Fan Mode Correct
|
Yes
|
|
Space Temperature Acceptable
|
Yes
|
Misc. Comments
Work Order: 174179
Work Order Number(s)
174179
Issues found durring this assessment have been assigned to the above
work order(s).