Assessor
Hummy Khan
Date
Outdoor Temperature
61°F
Relative Humidity
66%
Outdoor Dew Point
50°F
Air Handling Unit (Assess representative sample of RTU/AHU, including Portables)
Check | OK | Comments |
---|---|---|
Tag Number | ||
Displayed
|
No
|
Non of the exhaust fans appear to have tag numbers.
|
Status | ||
Running
|
Yes
|
Check | OK | Comments |
---|---|---|
Outdoor Pollution | ||
Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
|
Yes
|
|
Louvers and Access Doors | ||
Operating properly
|
No
|
RTU-7 Unable to open up the access door to mixing plenum. Door handle is loose and needs to be screwed in properly.
|
Deflectors & Screens | ||
Present
|
Yes
|
|
No debris
|
Yes
|
|
Dampers | ||
Outside air damper: no obstructions
|
No
|
RTU-5, 8, 9 - Outside air dampers appear to be 100% closed. RTU-4 and 6 - Outside air dampers barely open compared to some of the other units.
|
Return air damper: no obstructions
|
Yes
|
Check | OK | Comments |
---|---|---|
Clean | ||
No excess dirt, not used for storage
|
No
|
All units need thorough cleaning.
|
Insulation | ||
Secure and Clean
|
Yes
|
|
P-Trap (if present) | ||
Charged with liquid
|
Yes
|
Check | OK | Comments |
---|---|---|
Filters | ||
Free of any bypassing
|
No
|
Munters RTU-Air bypass due to filters off track. RTU-K-RM- Filter end cover plate missing creating air bypass.
|
Correct size
|
Yes
|
|
Free from excessive loading, dampness or odor
|
Yes
|
|
Not collapsed/not fallen off
|
No
|
Munters RTU- Two filters were off the track and I tried to put them back in place. Not sure how long they are going to stay on track. The need to be properly installed by an HVAC Technician.
|
Present (not missing)
|
Yes
|
|
Date and initials written
|
Yes
|
|
Heating Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Cooling Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Access: Free of any obstructions in area that may affect access
|
Yes
|
|
Condensation: No excess condensation problems
|
Yes
|
|
Blowoff: Free of water from coil blowoff
|
Yes
|
|
Condensate Pan and Drain Line | ||
No visible bacterial or fungal growth
|
Yes
|
|
Clean, no residue, no standing water
|
Yes
|
|
No Overflow, leakage, blockage, or damage
|
Yes
|
|
Proper slope, drain line ok, drainage acceptable, discharge okay
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Operational
|
No
|
OARTU-3- Exhaust fan in the unit not running.
|
No unusual odors, noise, or vibration
|
No
|
Exhaust fan near Munters Rooftop unit on high roof is making loud noise.
|
Check | OK | Comments |
---|---|---|
Chilled Water Central Plant | ||
Cooling tower operational
|
No
|
Not operational due to winter mode.
|
Heating Central Plant | ||
Boiler operational
|
Yes
|
Check | OK | Comments |
---|---|---|
Thermostat | ||
Thermostat setting acceptable
|
Yes
|
|
Thermostat cover
|
Yes
|
|
Fan Mode Correct
|
Yes
|
|
Space Temperature Acceptable
|
Yes
|
Misc. Comments
Work Order: 169717
Work Order Number(s)
169717
Issues found durring this assessment have been assigned to the above
work order(s).