School
| Check | OK | Comments |
|---|---|---|
| Tag Number | ||
Displayed
|
Yes
|
|
| Status | ||
Running
|
Yes
|
|
| Check | OK | Comments |
|---|---|---|
| Outdoor Pollution | ||
Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
|
Yes
|
|
| Louvers and Access Doors | ||
Operating properly
|
Yes Work Order Closed by Building Maintenance
|
AHU-3- Latch for the access door to outside air section bent and the door is not latched in.
|
| Deflectors & Screens | ||
Present
|
Yes
|
|
No debris
|
Yes
|
|
| Dampers | ||
Outside air damper: no obstructions
|
Yes Work Order Closed by Building Maintenance
|
AHU-4 - Not all damper blades of the outside air dampers appeared to be open in the same position and should be checked for proper operation by an HVAC technician.
|
Return air damper: no obstructions
|
Yes
|
|
Assessor
Hummy Khan
Date
| Check | OK | Comments |
|---|---|---|
| Clean | ||
No excess dirt, not used for storage
|
Yes Work Order Closed by Building Maintenance
|
On all units-Outside air intake louvers that are part of the access door to outside air intake section dirty and needs to be cleaned.
|
| Insulation | ||
Secure and Clean
|
Yes
|
|
| P-Trap (if present) | ||
Charged with liquid
|
Yes
|
|
Outdoor Temperature
54°F
| Check | OK | Comments |
|---|---|---|
| Filters | ||
Free of any bypassing
|
Yes
|
|
Correct size
|
Yes
|
|
Free from excessive loading, dampness or odor
|
Yes
|
|
Not collapsed/not fallen off
|
Yes
|
|
Present (not missing)
|
Yes
|
|
Date and initials written
|
Yes Work Order Closed by Building Maintenance
|
No installation dates and name initials of the installing technician on many units' pre-filters.
|
| Heating Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
| Cooling Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Access: Free of any obstructions in area that may affect access
|
Yes
|
|
Condensation: No excess condensation problems
|
Yes
|
|
Blowoff: Free of water from coil blowoff
|
Yes
|
|
| Condensate Pan and Drain Line | ||
No visible bacterial or fungal growth
|
Yes
|
|
Clean, no residue, no standing water
|
Yes
|
|
No Overflow, leakage, blockage, or damage
|
Yes
|
|
Proper slope, drain line ok, drainage acceptable, discharge okay
|
Yes
|
|
Relative Humidity
90%
| Check | OK | Comments |
|---|---|---|
| Condition | ||
Operational
|
Yes
|
|
No unusual odors, noise, or vibration
|
Yes
|
|
Outdoor Dew Point
51°F
| Check | OK | Comments |
|---|---|---|
| Heating Central Plant | ||
Boiler operational
|
Yes
|
|
Misc. Comments
A golden yellowish motor sitting on the roof and looks like it's abandoned and should be removed.
Work Order Number(s)
258433
Issues found durring this assessment have been assigned to the above
work order(s).