Assessor
          Jeffrey Klenk
        Date
              Outdoor Temperature
              52°F
          Relative Humidity
              65%
          Outdoor Dew Point
              40°F
          Air Handling Unit (Assess representative sample of RTU/AHU, including Portables)
| Check | OK | Comments | 
|---|---|---|
| Tag Number | ||
| 
        Displayed
         | Yes | |
| Status | ||
| 
        Running
         | Yes | |
| Check | OK | Comments | 
|---|---|---|
| Outdoor Pollution | ||
| 
        Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
         | Yes | |
| Louvers and Access Doors | ||
| 
        Operating properly
         | Yes | |
| Deflectors & Screens | ||
| 
        Present
         | Yes | |
| 
        No debris
         | Yes | |
| Dampers | ||
| 
        Outside air damper: no obstructions
         | Yes Work Order Closed by Building Maintenance | 
        Cafeteria Addition RTU and ACU-1 - The outdoor air dampers appeared closed.
         | 
| 
        Return air damper: no obstructions
         | Yes | |
| Check | OK | Comments | 
|---|---|---|
| Clean | ||
| 
        No excess dirt, not used for storage
         | Yes | |
| Insulation | ||
| 
        Secure and Clean
         | Yes | |
| P-Trap (if present) | ||
| 
        Charged with liquid
         | Yes | |
| Check | OK | Comments | 
|---|---|---|
| Filters | ||
| 
        Free of any bypassing
         | Yes | |
| 
        Correct size
         | Yes | |
| 
        Free from excessive loading, dampness or odor
         | Yes | |
| 
        Not collapsed/not fallen off
         | Yes | |
| 
        Present (not missing)
         | Yes | |
| 
        Date and initials written
         | Yes | |
| Heating Coils | ||
| 
        Clean, no noticeable leaks, or obstructions
         | Yes | |
| Cooling Coils | ||
| 
        Clean, no noticeable leaks, or obstructions
         | Yes | |
| 
        Access: Free of any obstructions in area that may affect access
         | Yes | |
| 
        Condensation: No excess condensation problems
         | Yes | |
| 
        Blowoff: Free of water from coil blowoff
         | Yes | |
| Condensate Pan and Drain Line | ||
| 
        No visible bacterial or fungal growth
         | Yes | |
| 
        Clean, no residue, no standing water
         | Yes | |
| 
        No Overflow, leakage, blockage, or damage
         | Yes | |
| 
        Proper slope, drain line ok, drainage acceptable, discharge okay
         | Yes | |
| Check | OK | Comments | 
|---|---|---|
| Condition | ||
| 
        Operational
         | Yes Work Order Closed by Building Maintenance | 
        A few exhaust fans were not operating per the exterior inspection of units located on the roof.  
         | 
| 
        No unusual odors, noise, or vibration
         | Yes Work Order Closed by Building Maintenance | 
        The fan belt in RTU-2 did not appear tight causing "wobble" (loss of efficiency).
         | 
| Check | OK | Comments | 
|---|---|---|
| Heating Central Plant | ||
| 
        Boiler operational
         | Yes | |
Misc. Comments
              Time of inspection 9:00 - 9:35 am.
          Work Order Number(s)
                    232313
      
          
        Issues found durring this assessment have been assigned to the above
        work order(s).
      
    