School
Assessor
Hummy Khan
Date
Outdoor Temperature
48°F
Relative Humidity
79%
Outdoor Dew Point
41°F
Air Handling Unit (Assess representative sample of RTU/AHU, including Portables)
Check | OK | Comments |
---|---|---|
Tag Number | ||
Displayed
|
No
|
No tag numbers on a few exhaust fans and three large Trane split system rooftop units.
|
Status | ||
Running
|
No
|
ACU-1 & AHU-3 not running.
|
Check | OK | Comments |
---|---|---|
Outdoor Pollution | ||
Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
|
Yes
|
|
Louvers and Access Doors | ||
Operating properly
|
Yes
|
|
Deflectors & Screens | ||
Present
|
Yes
|
|
No debris
|
Yes
|
|
Dampers | ||
Outside air damper: no obstructions
|
No
|
AHU-6 and ACU-3 - Outside air dampers closed. ACU-2 & ACU-4-Outside air dampers less open when compared to other units.
|
Return air damper: no obstructions
|
Yes
|
Check | OK | Comments |
---|---|---|
Clean | ||
No excess dirt, not used for storage
|
No
|
ACU-4- Empty can of rust inhibitor stored in the mixing plenum. Removed it and threw it away while on site. OAAHU-2 - Hose stored inside mixing section.
|
Insulation | ||
Secure and Clean
|
Yes
|
|
P-Trap (if present) | ||
Charged with liquid
|
Yes
|
Check | OK | Comments |
---|---|---|
Filters | ||
Free of any bypassing
|
No
|
AHU-5- Air bypass around filters.
|
Correct size
|
Yes
|
|
Free from excessive loading, dampness or odor
|
Yes
|
|
Not collapsed/not fallen off
|
No
|
Large Trane split system rooftop unit (No tag number) - In one unit the filter is bent and in another, one filter is collapsing.
|
Present (not missing)
|
Yes
|
|
Date and initials written
|
No
|
None of the filters have initials of the installing technician.
|
Heating Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Cooling Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Access: Free of any obstructions in area that may affect access
|
Yes
|
|
Condensation: No excess condensation problems
|
Yes
|
|
Blowoff: Free of water from coil blowoff
|
Yes
|
|
Condensate Pan and Drain Line | ||
No visible bacterial or fungal growth
|
Yes
|
|
Clean, no residue, no standing water
|
Yes
|
|
No Overflow, leakage, blockage, or damage
|
Yes
|
|
Proper slope, drain line ok, drainage acceptable, discharge okay
|
No
|
Three Trane large split system units (No tag number) - Condensing drain improperly terminated.
|
Check | OK | Comments |
---|---|---|
Condition | ||
Operational
|
No
|
Exhaust fan EF-3, 10, 12 & 15 - Not working. Another large exhaust fan (no tag number) near mechanical penthouse - Not running.
|
No unusual odors, noise, or vibration
|
Yes
|
Check | OK | Comments |
---|---|---|
Chilled Water Central Plant | ||
Chiller operational
|
Yes
|
Not operational due to heating season.
|
Cooling tower operational
|
Yes
|
Not operational due to heating season.
|
Heating Central Plant | ||
Boiler operational
|
Yes
|
Check | OK | Comments |
---|---|---|
Thermostat | ||
Thermostat setting acceptable
|
No
|
Portable #120- Replace battery message displayed on thermostat. Portable # 52-Thermostat display blank. Rooms in Villa # V130, V131, V132, V133- Thermostats in alarm. Room #V131, V136, V137, V138 -Change filter message displayed on thermostat. Portable# 124-Cooling set point set at 72 deg instead of 74 deg.
|
Thermostat cover
|
No
|
Portable # 120- Lock missing from the front cover and tape used instead. Portable # 81, 121, 125, and rooms in Villa # V130, V131, V134 - Thermostat cover missing. Portable # 52 - Front cover missing, found it laying on a chair, reinstalled it while on site. Room #V136-(Villa) Thermostat cover has a hole and seems to have been vandalized.
|
Fan Mode Correct
|
Yes
|
|
Space Temperature Acceptable
|
No
|
Portable #121- Maintaining occupied set point of 70 deg while unoccupied.
|
Work Order Number(s)
183485
Issues found durring this assessment have been assigned to the above
work order(s).
New packed ductless split system condensing unit sitting on roof and not installed.
Tarp placed underneath a valve in the mechanical penthouse to catch leaking water.
Work Order: 183485