Indoor Environmental Quality HVAC Assessment of Folly Quarter Middle School: January 20th, 2021 (HXFQMS202100002E)

Assessor
Hummy Khan
Date
Outdoor Temperature
43°F
Relative Humidity
35%
Outdoor Dew Point
18°F

Air Handling Unit (Assess representative sample of RTU/AHU, including Portables)

Unit
Check OK Comments
Tag Number
Displayed
No
Exhaust Fans - No tags numbers.
Status
Running
Yes
Outdoor Air Intake and Outdoor Air Dampers
Check OK Comments
Outdoor Pollution
Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
Yes
Louvers and Access Doors
Operating properly
Yes
Deflectors & Screens
Present
Yes
No debris
Yes
Dampers
Outside air damper: no obstructions
No
AHU-4 and AHU-5 - Outside air dampers closed.
Return air damper: no obstructions
Yes
Mixing Plenum
Check OK Comments
Clean
No excess dirt, not used for storage
Yes
Insulation
Secure and Clean
Yes
P-Trap (if present)
Charged with liquid
Yes
Filters and Coils
Check OK Comments
Filters
Free of any bypassing
No
AHU-4 and AHU-5 - End blank cover plates laying on the floor of the units and not installed creating air bypass around filters. Cover plates were installed while on site. Venmar OAU-2 air bypass around final filters.
Correct size
Yes
Free from excessive loading, dampness or odor
Yes
Not collapsed/not fallen off
Yes
Present (not missing)
Yes
Date and initials written
No
No technician 's initials on filters installing the filters.
Heating Coils
Clean, no noticeable leaks, or obstructions
Yes
Cooling Coils
Clean, no noticeable leaks, or obstructions
Yes
Access: Free of any obstructions in area that may affect access
Yes
Condensation: No excess condensation problems
Yes
Blowoff: Free of water from coil blowoff
Yes
Condensate Pan and Drain Line
No visible bacterial or fungal growth
Yes
Clean, no residue, no standing water
Yes
No Overflow, leakage, blockage, or damage
Yes
Proper slope, drain line ok, drainage acceptable, discharge okay
No
Condensate drain on all units - Improperly terminated.
Fans and Motors
Check OK Comments
Condition
Operational
No
Approximately ten exhaust fans near Venmar OAU-1 and 2 - Not running.
No unusual odors, noise, or vibration
No
Exhaust fan near AHU-1 - Rattling.
Central Plant
Check OK Comments
Heating Central Plant
Boiler operational
Yes
Misc. Comments
Work Order #178336
Work Order Number(s)
178336
Issues found durring this assessment have been assigned to the above work order(s).