Indoor Environmental Quality HVAC Assessment of Deep Run Elementary School: November 4th, 2020 (HXDRES2020000017)

Assessor
Hummy Khan
Date
Outdoor Temperature
57°F
Relative Humidity
50%
Outdoor Dew Point
39°F

Air Handling Unit (Assess representative sample of RTU/AHU, including Portables)

Unit
Check OK Comments
Tag Number
Displayed
Yes
Status
Running
No
AHU-2 (in penthouse) - Not running. RTU-2, 3, 4-Exhaust/relief fan of the unit not running.
Outdoor Air Intake and Outdoor Air Dampers
Check OK Comments
Outdoor Pollution
Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
Yes
Louvers and Access Doors
Operating properly
Yes
Deflectors & Screens
Present
Yes
No debris
Yes
Dampers
Outside air damper: no obstructions
No
RTU-3, 4, 7 & ACU-1, 2 - Outside air dampers appear to be closed.
Return air damper: no obstructions
No
RTU-7, 10, & 11 (Munters) - Relief/exhaust dampers 100% closed.
Mixing Plenum
Check OK Comments
Clean
No excess dirt, not used for storage
Yes
Insulation
Secure and Clean
Yes
P-Trap (if present)
Charged with liquid
Yes
Filters and Coils
Check OK Comments
Filters
Free of any bypassing
Yes
Correct size
Yes
Free from excessive loading, dampness or odor
Yes
Not collapsed/not fallen off
Yes
Present (not missing)
No
RTU-2, 3, 4- Pre-filters missing. AHU-2 - Final filter missing.
Date and initials written
Yes
Heating Coils
Clean, no noticeable leaks, or obstructions
Yes
Cooling Coils
Clean, no noticeable leaks, or obstructions
Yes
Access: Free of any obstructions in area that may affect access
Yes
Condensation: No excess condensation problems
Yes
Blowoff: Free of water from coil blowoff
Yes
Condensate Pan and Drain Line
No visible bacterial or fungal growth
Yes
Clean, no residue, no standing water
Yes
No Overflow, leakage, blockage, or damage
Yes
Proper slope, drain line ok, drainage acceptable, discharge okay
No
ACU-1 & 2 condensate drain improperly terminated.
Fans and Motors
Check OK Comments
Condition
Operational
No
Exhaust fan # 6 not running.
No unusual odors, noise, or vibration
No
RTU-9 (Munters) relief/exhaust fan noisy compare to other units.
Central Plant
Check OK Comments
Heating Central Plant
Boiler operational
Yes
Portable(s)
Check OK Comments
Thermostat
Thermostat setting acceptable
Yes
Thermostat cover
Yes
Fan Mode Correct
Yes
Space Temperature Acceptable
Yes
Misc. Comments
Work Order: 173169
Work Order Number(s)
173169
Issues found durring this assessment have been assigned to the above work order(s).