Assessor
Hummy Khan
Date
Outdoor Temperature
70°F
Relative Humidity
92%
Outdoor Dew Point
66°F
Air Handling Unit (Assess representative sample of RTU/AHU, including Portables)
Check | OK | Comments |
---|---|---|
Tag Number | ||
Displayed
|
No
|
Appears to be no tags numbers on any exhaust fans.
|
Status | ||
Running
|
Yes
|
Check | OK | Comments |
---|---|---|
Outdoor Pollution | ||
Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
|
Yes
|
|
Louvers and Access Doors | ||
Operating properly
|
Yes
|
|
Deflectors & Screens | ||
Present
|
Yes
|
|
No debris
|
Yes
|
|
Dampers | ||
Outside air damper: no obstructions
|
No
|
RTU-MP, RTU-O, RTU-MC- outdoor air dampers barely open. RTU-SE- outdoor air dampers open very little compare to some of the other units.
|
Return air damper: no obstructions
|
Yes
|
Check | OK | Comments |
---|---|---|
Clean | ||
No excess dirt, not used for storage
|
No
|
All Units - Need cleaning.
|
Insulation | ||
Secure and Clean
|
Yes
|
|
P-Trap (if present) | ||
Charged with liquid
|
Yes
|
Check | OK | Comments |
---|---|---|
Filters | ||
Free of any bypassing
|
Yes
|
|
Correct size
|
Yes
|
|
Free from excessive loading, dampness or odor
|
Yes
|
|
Not collapsed/not fallen off
|
Yes
|
|
Present (not missing)
|
Yes
|
|
Date and initials written
|
Yes
|
|
Heating Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Cooling Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Access: Free of any obstructions in area that may affect access
|
Yes
|
|
Condensation: No excess condensation problems
|
Yes
|
|
Blowoff: Free of water from coil blowoff
|
Yes
|
|
Condensate Pan and Drain Line | ||
No visible bacterial or fungal growth
|
Yes
|
|
Clean, no residue, no standing water
|
No
|
|
No Overflow, leakage, blockage, or damage
|
No
|
RTU-SE and RTU-O- Condensate drain not properly connected and leaking water on the roof.
|
Proper slope, drain line ok, drainage acceptable, discharge okay
|
No
|
Condensate drain lines on three rooftop units are not running to the roof drain.
|
Check | OK | Comments |
---|---|---|
Condition | ||
Operational
|
Yes
|
|
No unusual odors, noise, or vibration
|
No
|
Exhaust fan near RTU-O is rattling. Large exhaust fan appears to be for the kitchen- the hood is missing, partially covered with tarp and cardboard boxes sitting on top of it.
|
Check | OK | Comments |
---|---|---|
Heating Central Plant | ||
Boiler operational
|
Yes
|
Check | OK | Comments |
---|---|---|
Thermostat | ||
Thermostat setting acceptable
|
No
|
Portable 113 and 204-Low battery symbol on the thermostat display.
|
Thermostat cover
|
No
|
Portable 257 and 258- Missing thermostat guard.
|
Fan Mode Correct
|
Yes
|
|
Space Temperature Acceptable
|
Yes
|
Work Order Number(s)
169380
Issues found durring this assessment have been assigned to the above
work order(s).
Work Order: 169380