School
Assessor
Christopher Madden
Date
Air Distribution and Terminal System (Assess 2-3 Locations per HVAC Zone)
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, noise or vibration
|
Yes
|
|
Clean, no obstructions
|
Yes
|
|
Free from signs of moisture/mold, insects or rodents?
|
Yes
|
|
No noticeable air leaks
|
Yes
|
Check | OK | Comments |
---|---|---|
Ceiling Tiles | ||
Tight seal on all tiles
|
Yes
|
|
No stained/damaged tiles indicating high RH or moisture problem
|
Yes
|
|
Insulation & Fireproofing | ||
Condition okay
|
No
|
Storage Room across from 218 - Water stained pipe insulation (no visible mold growth, WO #198210).
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors or unusual sounds
|
Yes
|
|
Clean, no excess dirt or moisture
|
Yes
|
|
No obstruction to air flow
|
Yes
|
|
No purposely placed obstruction indicating occupant distress
|
Yes
|
|
Location | ||
No short circuiting between supply and return
|
Yes
|
|
Doors | ||
Doors not tight or difficult to close indicating large pressure differential
|
Yes
|
Building
Check | OK | Comments |
---|---|---|
Foundation | ||
No moisture penetration or signs of mold?
|
Yes
|
|
Doors and Windows | ||
Caulking and weather stripping in good condition
|
No
|
205, 207, and 99 - Condensation in windows, probably seal issue (WO #198212). 221- Interior window caulk deteriorating (WO #198216).
|
Check | OK | Comments |
---|---|---|
Condition | ||
Room is free of dust and clutter
|
Yes
|
|
No stained or damage ceiling tiles
|
No
|
Outside 229, Outside 231, 120, Media Office (M2), 175, 301 (Storage), 143 - Stained Ceiling Tile
|
No visible mold present (walls, cabinets, under sinks, behind posters)
|
Yes
|
|
Relative Humidity | ||
Not above 70%
|
No
|
99 and 102- Elevated humidity (75.8-78.8%). Building Maintenance shutdown outside air units to prevent humid outside air from entering through HVAC system. FCU's continued to run to provide cooling. The Office of the Environment is to monitor the left wing over the summer as this is a re-occurring issue.
|
Check | OK | Comments |
---|---|---|
Condition | ||
Clean
|
No
|
S-21 (near gym) - Compressor leaking and missing/damaged fiberglass pipe insulation (WO #198214).
|
No unusual noise or odor
|
Yes
|
|
No mold growth on insulation
|
Yes
|
|
Traps contain water
|
Yes
|
|
Chemical Storage | ||
Containers capped
|
Yes
|
|
No evidence of an active spill
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, or unusual noise or vibration
|
Yes
|