Air Distribution and Terminal System (Assess 2-3 Locations per HVAC Zone)
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, noise or vibration
|
No
|
Portable 74 had a strong air freshener scent upon entering. A plug-in was observed and discarded by the inspector. School administration is to remind staff that air fresheners are not permitted in the classroom as it can be an irritant to others and could mask an odor of concern.
Portable 107 had the general inherent aroma associated with such constructed portable prototypes. No action required.
|
Clean, no obstructions
|
Yes
|
|
Free from signs of moisture/mold, insects or rodents?
|
Yes
|
|
No noticeable air leaks
|
Yes
|
|
Duct Lining | ||
No dirt, dampness, or mold
|
No
|
Portable 74 had damp/wet sound liner in the HVAC unit on the right side. Work Order 165598.
|
No Deterioration
|
Yes
|
Check | OK | Comments |
---|---|---|
Ceiling Tiles | ||
Tight seal on all tiles
|
Yes
|
|
No stained/damaged tiles indicating high RH or moisture problem
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors or unusual sounds
|
Yes
|
|
Clean, no excess dirt or moisture
|
No
|
Air filters were in need of attention in portables 74 (replacement and out of position), 106 (replacement), and 107 (replacement). Work Order 165598.
|
No obstruction to air flow
|
Yes
|
|
No purposely placed obstruction indicating occupant distress
|
Yes
|
|
Location | ||
No short circuiting between supply and return
|
Yes
|
|
Doors | ||
Doors not tight or difficult to close indicating large pressure differential
|
Yes
|
Building
Check | OK | Comments |
---|---|---|
Foundation | ||
No moisture penetration or signs of mold?
|
Yes
|
|
Doors and Windows | ||
Caulking and weather stripping in good condition
|
No
|
Portable 74 has a hole in the drywall where a previous HVAC thermostat had been removed. Work Order 165599.
Portable 106 - the bottom right drywall of the door located near the fire extinguisher was considered wet via a moisture meter. Further inspection and assessment required. Work Order 165599.
|
Check | OK | Comments |
---|---|---|
Condition | ||
Room is free of dust and clutter
|
Yes
|
|
No stained or damage ceiling tiles
|
No
|
Several ceiling tiles were water stained and may be a result of the ongoing roof replacement project. Some noted areas included hallways (outside of electrical room near kitchen door, outside room 12, and near AED at kitchen door, outside of cafeteria doors nearest the stage) and rooms 108 & 121. If not already being address, contact project manager of roofing project and/or submit a work order to Building Services for tiles not related to the roofing project.
|
No visible mold present (walls, cabinets, under sinks, behind posters)
|
Yes
|
|
Relative Humidity | ||
Not above 70%
|
No
|
Room 106 was at 70% and was higher than other rooms served by same ventilation system type. Carpet had signs of topical moisture in random locations as determined by a moisture probe. A ceiling tile had been removed due to the roofing project and as a result, observed a void around pipes going through roof deck into a mechanical unit and/or room (may be contributing to increased relative humidity). Work Order 165596.
|
Check | OK | Comments |
---|---|---|
Condition | ||
Clean
|
Yes
|
|
No unusual noise or odor
|
Yes
|
|
No mold growth on insulation
|
Yes
|
|
Traps contain water
|
Yes
|
|
Chemical Storage | ||
Containers capped
|
Yes
|
|
No evidence of an active spill
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, or unusual noise or vibration
|
No
|
Due to roofing replacement project, some wall unit ventilators on the second floor, such as room 204, had their power disconnected and unit removed away from the wall.
|