Assessor
Jeffrey Klenk
Date
Air Distribution and Terminal System (Assess 2-3 Locations per HVAC Zone)
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, noise or vibration
|
Yes
|
|
Clean, no obstructions
|
Yes
|
|
Free from signs of moisture/mold, insects or rodents?
|
Yes
|
|
No noticeable air leaks
|
Yes
|
Check | OK | Comments |
---|---|---|
Ceiling Tiles | ||
Tight seal on all tiles
|
Yes
|
|
No stained/damaged tiles indicating high RH or moisture problem
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors or unusual sounds
|
Yes
|
|
Clean, no excess dirt or moisture
|
Yes Work Order Closed by Building Maintenance
|
Cafeteria air supply diffusers have visible grime and dust accumulation on them that requires the Custodial High Surface Cleaning crew to address (WO #222316).
|
No obstruction to air flow
|
Yes
|
|
No purposely placed obstruction indicating occupant distress
|
Yes Work Order Closed by Building Maintenance
|
The front office reception area has a lamp somewhat near the area's thermostat. If thermal discomfort has been experienced it could be due to the heat from the lamp giving a false impression of the air temperature within the area. If the case, school administration is to move the lamp away from the thermostat.
|
Location | ||
No short circuiting between supply and return
|
Yes Work Order Closed by Building Maintenance
|
Room 171 - A supply air diffuser is too close to the air return grille (WO #222318).
|
Doors | ||
Doors not tight or difficult to close indicating large pressure differential
|
Yes
|
Building
Check | OK | Comments |
---|---|---|
Foundation | ||
No moisture penetration or signs of mold?
|
Yes
|
|
Doors and Windows | ||
Caulking and weather stripping in good condition
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Room is free of dust and clutter
|
Yes Work Order Closed by Building Maintenance
|
Room 141 (A/B) has aerosol disinfectant sprays which are not permitted because it would aerosolize a potential airborne irritant. Room 141 (A/B) also has a small shaggy rug under a table. Shag rugs can be harder to keep clean (a personal vacuum is in the room and assume teacher is regularly cleaning). School administration is to remove aerosol sprays and consider removing the rug if it does not serve an educational purpose since the room is already carpeted. Note, disinfectant wipes are permitted.
Room 119 had a food item accessible to rodents/pests, several small artificial plants (appear to be clean at the present time) on top of a cabinet, fabric items in a corner reading area and within a small pop tent/teepee (confined space), and an electric plastic kettle on the floor (plugged in and water in pitcher; has an auto shutoff safety feature once water boils). Food items are to be in a sturdy plastic container with a securable lid. The artificial plants are to be removed since they cannot be readily cleaned and under certain conditions form mold growth due to the laden dust. The fabric items are to be reduced or removed if they do not serve an educational purpose since they can harbor allergens (if not regularly cleaned; not custodial responsibility) and students are in close contact with the items. The electric kettle is more of a fire and safety concern (scalding water). The device is to be removed. The above corrective actions for room 119 are the responsibility of school administration.
The floor tile in the commons area of rooms 116-121 had heavy dirt build up from foot traffic from the secondary front entrance. This was also observed in the cafeteria near its exterior entrance/exit door. It was a non-school day the day of the inspection and not sure if evening custodial staff would normally clean the floor before the next school day. School custodial staff are to place additional walk off mats if feasible and/or clean impacted floors the evening or morning before school to reduce tracking of particulate.
|
No stained or damage ceiling tiles
|
Yes Work Order Closed by Building Maintenance
|
Water stained ceiling tiles were observed in room 156 and the boys restroom located in the commons of rooms 171 and 173. If not already being addressed, school custodial staff is to submit a work order to Building Services to assess, correct source, and replace ceiling tile.
|
No visible mold present (walls, cabinets, under sinks, behind posters)
|
Yes Work Order Closed by Building Maintenance
|
No mold observed, however the backsplash near the sink in room 195 has signs of water damage (WO #222317).
|
Relative Humidity | ||
Not above 70%
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Clean
|
Yes
|
|
No unusual noise or odor
|
Yes
|
|
No mold growth on insulation
|
Yes
|
|
Traps contain water
|
Yes
|
|
Chemical Storage | ||
Containers capped
|
Yes
|
|
No evidence of an active spill
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, or unusual noise or vibration
|
Yes
|
Work Order Number(s)
222316, 222317, 222318
Issues found durring this assessment have been assigned to the above
work order(s).