Assessor
Jeffrey Klenk
Date
Air Distribution and Terminal System (Assess 2-3 Locations per HVAC Zone)
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, noise or vibration
|
Yes
|
|
Clean, no obstructions
|
Yes
|
|
Free from signs of moisture/mold, insects or rodents?
|
Yes
|
|
No noticeable air leaks
|
Yes
|
Check | OK | Comments |
---|---|---|
Ceiling Tiles | ||
Tight seal on all tiles
|
Yes
|
|
No stained/damaged tiles indicating high RH or moisture problem
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors or unusual sounds
|
Yes
|
|
Clean, no excess dirt or moisture
|
No
|
Room 129. The backside of the exposed vanes/fins of the supply air diffusers have staining. School custodial staff is to clean the backs of the exposed fins until staining is removed.
|
No obstruction to air flow
|
No
|
Questionable air flow from certain supply air diffusers as determined by qualitative means (feel and/or an existing tissue strip adhered to diffuser). Rooms 116, 125, and common area of 140's Pod. Work order 173308.
|
No purposely placed obstruction indicating occupant distress
|
Yes
|
|
Location | ||
No short circuiting between supply and return
|
Yes
|
|
Doors | ||
Doors not tight or difficult to close indicating large pressure differential
|
Yes
|
Building
Check | OK | Comments |
---|---|---|
Foundation | ||
No moisture penetration or signs of mold?
|
Yes
|
|
Doors and Windows | ||
Caulking and weather stripping in good condition
|
No
|
Room 140. The second section/bay (going right to left) of the backcase along the exterior wall is showing potential moisture concerns via the use of a moitsure meter calibrated to wood. Work order 173307.
|
Check | OK | Comments |
---|---|---|
Condition | ||
Room is free of dust and clutter
|
Yes
|
|
No stained or damage ceiling tiles
|
No
|
A water stained ceiling tile observed near the handicap stage lift within the cafeteria. The stain is near a sensor within the tile. School custodial staff is to submit a work order to Building Services if not already being addressed.
|
No visible mold present (walls, cabinets, under sinks, behind posters)
|
Yes
|
|
Relative Humidity | ||
Not above 70%
|
Yes
|
Relative humidity 70-72% in cafeteria, gymnasium, rooms 129, 162, and 164. This is due to ventilation system design/operation and weather (steady rain, overcast, 68 degrees) at the time of inspection. This was confirmed in a discussion with Building Services HVAC Shop. This does not represent an IEQ concern due to the timing (Fall).
|
Check | OK | Comments |
---|---|---|
Condition | ||
Clean
|
Yes
|
|
No unusual noise or odor
|
Yes
|
|
No mold growth on insulation
|
Yes
|
|
Traps contain water
|
Yes
|
|
Chemical Storage | ||
Containers capped
|
Yes
|
|
No evidence of an active spill
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, or unusual noise or vibration
|
Yes
|