Air Distribution and Terminal System (Assess 2-3 Locations per HVAC Zone)
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, noise or vibration
|
Yes
|
|
Clean, no obstructions
|
Yes
|
|
Free from signs of moisture/mold, insects or rodents?
|
Yes
|
|
No noticeable air leaks
|
Yes
|
Check | OK | Comments |
---|---|---|
Ceiling Tiles | ||
Tight seal on all tiles
|
Yes
|
|
No stained/damaged tiles indicating high RH or moisture problem
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors or unusual sounds
|
Yes
|
|
Clean, no excess dirt or moisture
|
No
|
The exposed side of the air supply diffusers in 130, 131, and 134 had visible dust accumulation. School custodial staff is to clean the diffusers.
The wall air return air grille in room 134 has rust spotting. Work order 207226.
|
No obstruction to air flow
|
No
|
The louvers of the one air supply diffuser near the teacher's desk in room 153 were closed. The louvers were opened back up upon finding.
|
No purposely placed obstruction indicating occupant distress
|
Yes
|
|
Location | ||
No short circuiting between supply and return
|
Yes
|
|
Doors | ||
Doors not tight or difficult to close indicating large pressure differential
|
Yes
|
Building
Check | OK | Comments |
---|---|---|
Foundation | ||
No moisture penetration or signs of mold?
|
Yes
|
|
Doors and Windows | ||
Caulking and weather stripping in good condition
|
No
|
An air gap was observed around the phone attached to the block wall (at classroom door) in room 131. A hole was in the block wall in the storage area in room 131. Work order 207225.
|
Check | OK | Comments |
---|---|---|
Condition | ||
Room is free of dust and clutter
|
No
|
Air freshener detected and observed in the storage closet of room 134. School administration is to remove and remind staff that air fresheners are not permitted since they can mask an odor of concern or be an irritant to others.
|
No stained or damage ceiling tiles
|
No
|
Water stained ceiling tile observed in room 189. If not already being addressed, school custodial staff is to submit a work order to Building Services to evaluate, correct leak, and replace ceiling tile.
|
No visible mold present (walls, cabinets, under sinks, behind posters)
|
No
|
Mold growth was observed on a few items in the storage closet in room 34 and wood playing blocks in rooms 130 and 131. Contractor utilized to clean / disinfect materials. Work order 207103 to review ventilation systems serving impacted rooms.
|
Relative Humidity | ||
Not above 70%
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Clean
|
Yes
|
|
No unusual noise or odor
|
Yes
|
|
No mold growth on insulation
|
Yes
|
|
Traps contain water
|
Yes
|
|
Chemical Storage | ||
Containers capped
|
Yes
|
|
No evidence of an active spill
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, or unusual noise or vibration
|
Yes
|