Assessor
Jeffrey Klenk
Date
Air Distribution and Terminal System (Assess 2-3 Locations per HVAC Zone)
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, noise or vibration
|
Yes
|
|
Clean, no obstructions
|
Yes
|
|
Free from signs of moisture/mold, insects or rodents?
|
Yes
|
|
No noticeable air leaks
|
Yes
|
Check | OK | Comments |
---|---|---|
Ceiling Tiles | ||
Tight seal on all tiles
|
Yes
|
|
No stained/damaged tiles indicating high RH or moisture problem
|
Yes
|
|
Insulation & Fireproofing | ||
Condition okay
|
No
|
Building Services HVAC Shop indicated a day or so before the IEQ inspection that pipe insulation was sweating and they turned off the chiller as a result. Two locations of isolated mold growth were observed on pipe insulation - in hallway outside of cafeteria and staff lounge. HVAC Shop has a contractor repairing several locations. The two locations with mold will be addressed by Office of Environment by disinfecting and painting with a mold inhibitor encapsulant.
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors or unusual sounds
|
Yes
|
|
Clean, no excess dirt or moisture
|
No
|
The HVAC ceiling cassette is dirty. Work Order 164777.
The back side of the supply air diffsuer fins are dirty and require custodial staff to clean. Observed in rooms 103, 13, and health suite.
|
No obstruction to air flow
|
Yes
|
|
No purposely placed obstruction indicating occupant distress
|
Yes
|
|
Location | ||
No short circuiting between supply and return
|
Yes
|
|
Doors | ||
Doors not tight or difficult to close indicating large pressure differential
|
Yes
|
Building
Check | OK | Comments |
---|---|---|
Foundation | ||
No moisture penetration or signs of mold?
|
Yes
|
|
Doors and Windows | ||
Caulking and weather stripping in good condition
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Room is free of dust and clutter
|
Yes
|
|
No stained or damage ceiling tiles
|
No
|
The chilled water pipe is failing thus forming condensate. Since Building Services is aware, as a result, obvious water stained ceiling tiles were observed. However, water staining was observed in 123 (near return air grille) and 176 (media work room) that may be missed since minor and in remote areas. Custodial staff is to submit a work order for these stained tiles unless already being addressed.
|
No visible mold present (walls, cabinets, under sinks, behind posters)
|
Yes
|
|
Relative Humidity | ||
Not above 70%
|
No
|
Building Services HVAC Shop indicated a day or so before the IEQ inspection that pipe insulation was sweating and they turned off the chiller as a result. Rooms 154 and 157 were over 70%. Office of Environment will be performing a periodic inspection of the building for relative humidity mold growth until Building Services is able to turn back on the chiller.
|
Check | OK | Comments |
---|---|---|
Condition | ||
Clean
|
Yes
|
|
No unusual noise or odor
|
Yes
|
|
No mold growth on insulation
|
Yes
|
|
Traps contain water
|
Yes
|
|
Chemical Storage | ||
Containers capped
|
Yes
|
|
No evidence of an active spill
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, or unusual noise or vibration
|
Yes
|