Indoor Environmental Quality General Assessment of Stevens Forest Elementary School: May 12th, 2021 (GXSFES2021000047)

Ductwork (Supply and Return)
Check OK Comments
Condition
No odors, noise or vibration
Yes
Clean, no obstructions
Yes
Free from signs of moisture/mold, insects or rodents?
No
Room 12 - Discoloration/Grime on ceiling around return air grille. Custodian is to attempt to clean. If that does not remove the material, please submit a work order for it to be painted so it is not mistaken for mold growth. Moisture meter readings indicate the ceiling is dry.
No noticeable air leaks
Yes
Envelope
Check OK Comments
Foundation
No moisture penetration or signs of mold?
Yes
Doors and Windows
Caulking and weather stripping in good condition
No
Portable 103 - Caulk gap to left of front door (WO #192638).
Plenum
Check OK Comments
Ceiling Tiles
Tight seal on all tiles
No
Exit Doors across from 75 - Missing Ceiling Tile.
No stained/damaged tiles indicating high RH or moisture problem
Yes
Classrooms (Assess 2 to 3 per HVAC System Zone)
Check OK Comments
Condition
Room is free of dust and clutter
Yes
No stained or damage ceiling tiles
No
Room 95 - Stained Ceiling Tile.
No visible mold present (walls, cabinets, under sinks, behind posters)
Yes
Relative Humidity
Not above 70%
Yes
Assessor
Christopher Madden
Date
Supply Diffusers, Return Grilles, Exhaust Grilles
Check OK Comments
Condition
No odors or unusual sounds
Yes
Clean, no excess dirt or moisture
Yes
No obstruction to air flow
Yes
No purposely placed obstruction indicating occupant distress
Yes
Location
No short circuiting between supply and return
Yes
Doors
Doors not tight or difficult to close indicating large pressure differential
Yes
Mechanical/Boiler Rooms (Assess Each)
Check OK Comments
Condition
Clean
Yes
No unusual noise or odor
Yes
No mold growth on insulation
Yes
Traps contain water
Yes
Chemical Storage
Containers capped
Yes
No evidence of an active spill
Yes
Fan Coil Units/VAV Boxes
Check OK Comments
Condition
No odors, or unusual noise or vibration
Yes