Assessor
Jeffrey Klenk
Date
Air Distribution and Terminal System (Assess 2-3 Locations per HVAC Zone)
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, noise or vibration
|
Yes
|
|
Clean, no obstructions
|
Yes
|
|
Free from signs of moisture/mold, insects or rodents?
|
Yes
|
|
No noticeable air leaks
|
Yes
|
Check | OK | Comments |
---|---|---|
Ceiling Tiles | ||
Tight seal on all tiles
|
No
|
Restroom in room 062 had ceiling tiles bowing or out of ceiling tile grid. School custodial staff is to reposition ceiling tiles. Submit a work order to Building Services if any difficulties.
Kiln room in art room 008 - the drywall ceiling has a ~2" x 6" void. Work order 181227.
|
No stained/damaged tiles indicating high RH or moisture problem
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors or unusual sounds
|
Yes
|
|
Clean, no excess dirt or moisture
|
No
|
Kiln room in art room 008 - the exhaust / return air grille is dirty and cob webs present.
Room 102 - the exposed side of the air supply diffusers had dirt or spotting from past condensate.
Rooms 71, 107, and 110: The back side of the air supply diffuser fins are dirty.
The above items are to be cleaned by school custodial staff.
|
No obstruction to air flow
|
Yes
|
|
No purposely placed obstruction indicating occupant distress
|
Yes
|
|
Location | ||
No short circuiting between supply and return
|
Yes
|
|
Doors | ||
Doors not tight or difficult to close indicating large pressure differential
|
Yes
|
Building
Check | OK | Comments |
---|---|---|
Foundation | ||
No moisture penetration or signs of mold?
|
No
|
About a foot of an expansion joint in the exterior brick is failing. Located to the far right end of the building when facing the school's main entrance. Near hose bib. Work order 181223.
|
Doors and Windows | ||
Caulking and weather stripping in good condition
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Room is free of dust and clutter
|
No
|
Media center has some fake plants on top of book cases.
Room 202 has several decorative items (tissue paper and lantern balls) hanging from the ceiling which collect dust and are disturbed by air flow coming from nearby supply air diffusers.
School administration is to determine if items have educational value and are maintained or need to be removed.
|
No stained or damage ceiling tiles
|
No
|
Kitchen office has a ceiling tile with a small water stain near the HVAC ceiling cassette. School custodial staff is to submit a work order to Building Services if not already being addressed.
|
No visible mold present (walls, cabinets, under sinks, behind posters)
|
Yes
|
|
Relative Humidity | ||
Not above 70%
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Clean
|
Yes
|
|
No unusual noise or odor
|
Yes
|
|
No mold growth on insulation
|
Yes
|
|
Traps contain water
|
Yes
|
|
Chemical Storage | ||
Containers capped
|
No
|
Classroom 062 has two unlabeled spray bottles (contains clear liquid) on top of cabinets above the sink. School is to determine contents. Label accordingly. If using Custodial Services products, label with manufacturer labels.
|
No evidence of an active spill
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, or unusual noise or vibration
|
Yes
|