Assessor
Christopher Madden
Date
Air Distribution and Terminal System (Assess 2-3 Locations per HVAC Zone)
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, noise or vibration
|
Yes
|
|
Clean, no obstructions
|
Yes
|
|
Free from signs of moisture/mold, insects or rodents?
|
Yes
|
|
No noticeable air leaks
|
Yes
|
|
Duct Lining | ||
No dirt, dampness, or mold
|
Yes Work Order Closed by Building Maintenance
|
Admin Conference Room - Pipe insulation wet due to leak (WO #249147). Building Maintenance to address cause. Pipe insulation to be replaced after the source of the leak has been corrected.
|
No Deterioration
|
Yes
|
Check | OK | Comments |
---|---|---|
Ceiling Tiles | ||
Tight seal on all tiles
|
Yes Work Order Closed by Building Maintenance
|
Room 128 - Ceiling tile out of place (fixed while onsite).
|
No stained/damaged tiles indicating high RH or moisture problem
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors or unusual sounds
|
Yes
|
|
Clean, no excess dirt or moisture
|
Yes
|
|
No obstruction to air flow
|
Yes
|
|
No purposely placed obstruction indicating occupant distress
|
Yes
|
|
Location | ||
No short circuiting between supply and return
|
Yes
|
|
Doors | ||
Doors not tight or difficult to close indicating large pressure differential
|
Yes
|
Building
Check | OK | Comments |
---|---|---|
Foundation | ||
No moisture penetration or signs of mold?
|
Yes
|
|
Doors and Windows | ||
Caulking and weather stripping in good condition
|
Yes Work Order Closed by Building Maintenance
|
Production Lab Storage - Daylight due to damaged door sweep (WO #249154).
|
Check | OK | Comments |
---|---|---|
Condition | ||
Room is free of dust and clutter
|
Yes Work Order Closed by Building Maintenance
|
Storage Room across from Mechanical Room A1 - Housekeeping/Clean floor of dust and clutter.
|
No stained or damage ceiling tiles
|
Yes Work Order Closed by Building Maintenance
|
Fitness Room (Off Gym, with washing machine/drier) - Stained Ceiling Tiles.
|
No visible mold present (walls, cabinets, under sinks, behind posters)
|
Yes
|
|
Relative Humidity | ||
Not above 70%
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Clean
|
Yes Work Order Closed by Building Maintenance
|
Mechanical Room A1 - Clean floor drain of debris. This could slow drainage if there is a leak within the boiler room.
|
No unusual noise or odor
|
Yes
|
|
No mold growth on insulation
|
Yes
|
|
Traps contain water
|
Yes
|
|
Chemical Storage | ||
Containers capped
|
Yes
|
|
No evidence of an active spill
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, or unusual noise or vibration
|
Yes Work Order Closed by Building Maintenance
|
Prep Room Next to Room 114 - The fume hood is in alarm. Please assess and place work order if needed.
|
Work Order Number(s)
249147, 249154
Issues found durring this assessment have been assigned to the above
work order(s).