Indoor Environmental Quality General Assessment of Mayfield Woods Middle School: November 19th, 2020 (GXMWMS202000002B)

Assessor
Christopher Madden
Date

Air Distribution and Terminal System (Assess 2-3 Locations per HVAC Zone)

Ductwork (Supply and Return)
Check OK Comments
Condition
No odors, noise or vibration
Yes
Clean, no obstructions
Yes
Free from signs of moisture/mold, insects or rodents?
Yes
No noticeable air leaks
Yes
Connections and Seals
Tight
Yes
Not Damaged or Dented
No
Band Closet - Diffuser fell through ceiling (WO #174064).
Plenum
Check OK Comments
Ceiling Tiles
Tight seal on all tiles
Yes
No stained/damaged tiles indicating high RH or moisture problem
Yes
Insulation & Fireproofing
Condition okay
No
Conference Room in Guidance - Minor water stained Stormwater pipe insulation (no mold growth). Work Order #174059.
Supply Diffusers, Return Grilles, Exhaust Grilles
Check OK Comments
Condition
No odors or unusual sounds
Yes
Clean, no excess dirt or moisture
No
Room 106, Locker Bank Outside of 106, 122, Outside of 203 - Supply diffusers dirty.
No obstruction to air flow
Yes
No purposely placed obstruction indicating occupant distress
Yes
Location
No short circuiting between supply and return
Yes
Doors
Doors not tight or difficult to close indicating large pressure differential
Yes

Building

Envelope
Check OK Comments
Foundation
No moisture penetration or signs of mold?
No
FACS - Window in exterior door appears to have a broken seal (WO #174063).
Doors and Windows
Caulking and weather stripping in good condition
Yes
Classrooms (Assess 2 to 3 per HVAC System Zone)
Check OK Comments
Condition
Room is free of dust and clutter
No
Room 213 - Non-issued furniture (couch).
No stained or damage ceiling tiles
No
Outside of 113, 114, Outside of 117, FACS (Above Drier) - Stained Ceiling Tile(s).
No visible mold present (walls, cabinets, under sinks, behind posters)
Yes
Relative Humidity
Not above 70%
Yes
Mechanical/Boiler Rooms (Assess Each)
Check OK Comments
Condition
Clean
Yes
No unusual noise or odor
Yes
No mold growth on insulation
Yes
Traps contain water
Yes
Chemical Storage
Containers capped
Yes
No evidence of an active spill
Yes
Fan Coil Units/VAV Boxes
Check OK Comments
Condition
No odors, or unusual noise or vibration
Yes