Assessor
Jeffrey Klenk
Date
Air Distribution and Terminal System (Assess 2-3 Locations per HVAC Zone)
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, noise or vibration
|
Yes
|
|
Clean, no obstructions
|
Yes
|
|
Free from signs of moisture/mold, insects or rodents?
|
Yes
|
|
No noticeable air leaks
|
Yes
|
Check | OK | Comments |
---|---|---|
Ceiling Tiles | ||
Tight seal on all tiles
|
Yes
|
|
No stained/damaged tiles indicating high RH or moisture problem
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors or unusual sounds
|
Yes
|
|
Clean, no excess dirt or moisture
|
No
|
The ceiling return grille in the computer lab (room 21) off the media center is dirty (on the side of the metal rails/grid). The back side of the exposed fins of the ceiling supply diffusers have staining in rooms 21, 26 (office), and 32. The perforated ceiling return air grilles at the entrance of the original gym are becoming clogged with particulate. School custodial staff are to clean the above items.
|
No obstruction to air flow
|
Yes
|
|
No purposely placed obstruction indicating occupant distress
|
Yes
|
|
Location | ||
No short circuiting between supply and return
|
Yes
|
|
Doors | ||
Doors not tight or difficult to close indicating large pressure differential
|
Yes
|
Building
Check | OK | Comments |
---|---|---|
Foundation | ||
No moisture penetration or signs of mold?
|
No
|
Portable 133 has a questionable moisture issue within the wall cavity to the right of the back door (non-ramp side). An inspection square was cut out of the drywall, no mold observed, but a noticeable damp odor was detected. About a 4' x 4' area of drywall was found to be wet or damp using a moisture meter. This section will be removed by Building Services for further inspection.
Work Order 194872.
|
Doors and Windows | ||
Caulking and weather stripping in good condition
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Room is free of dust and clutter
|
Yes
|
|
No stained or damage ceiling tiles
|
No
|
Dry brown water stained ceiling tiles were observed in room 21 (computer lab), hall outside room 254 (several stains and already red pinned), common area of pod outside room 39, and common area of pod outside room 50. If not already in progress, school custodial staff is to submit a work order for Building Services to assess, fix source, and replace ceiling tiles.
|
No visible mold present (walls, cabinets, under sinks, behind posters)
|
Yes
|
|
Relative Humidity | ||
Not above 70%
|
No
|
Computer lab (room 21) was initially 70% and teacher indicated the room can become humid. Office of Environment will place a data logger to record temperature and relative humidity to identify possible concerns. Portable 133 was 71%, but was attributed to a door being slightly propped open and inherent operation of the HVAC unit during damp humid morning.
|
Check | OK | Comments |
---|---|---|
Condition | ||
Clean
|
Yes
|
|
No unusual noise or odor
|
Yes
|
|
No mold growth on insulation
|
Yes
|
|
Traps contain water
|
Yes
|
|
Chemical Storage | ||
Containers capped
|
Yes
|
|
No evidence of an active spill
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, or unusual noise or vibration
|
Yes
|