Indoor Environmental Quality General Assessment of Long Reach High School: July 16th, 2021 (GXLRHS2021000056)

Assessor
Christopher Madden
Date

Air Distribution and Terminal System (Assess 2-3 Locations per HVAC Zone)

Ductwork (Supply and Return)
Check OK Comments
Condition
No odors, noise or vibration
No
Portable 50, 215, and 122 - Thermostat set to fan "on" which can lead to relative humidity mold growth (WO #198664). Room 339 - Exhaust fan rattling (check belts, bearings, etc., WO #198666).
Clean, no obstructions
Yes
Free from signs of moisture/mold, insects or rodents?
Yes
No noticeable air leaks
Yes
Plenum
Check OK Comments
Ceiling Tiles
Tight seal on all tiles
No
Foreign Language Portable - Several ceiling tiles not fitting properly.
No stained/damaged tiles indicating high RH or moisture problem
No
3rd Floor - Various Areas with Bowed Ceiling Tiles. The 3rd Floor is prone to elevated humidity in the summer (HVAC Contacted).
Supply Diffusers, Return Grilles, Exhaust Grilles
Check OK Comments
Condition
No odors or unusual sounds
Yes
Clean, no excess dirt or moisture
No
Dance Studio - Supply Diffusers Dirty (High Dusting Required).
No obstruction to air flow
Yes
No purposely placed obstruction indicating occupant distress
Yes
Location
No short circuiting between supply and return
Yes
Doors
Doors not tight or difficult to close indicating large pressure differential
Yes

Building

Envelope
Check OK Comments
Foundation
No moisture penetration or signs of mold?
Yes
Doors and Windows
Caulking and weather stripping in good condition
Yes
Classrooms (Assess 2 to 3 per HVAC System Zone)
Check OK Comments
Condition
Room is free of dust and clutter
No
B105 - There are two baked potatoes on a work bench that need to be discarded before they rot.
No stained or damage ceiling tiles
No
Outside 356, 335B, and Media (along TV Studio Wall) - Stained Ceiling Tile(s).
No visible mold present (walls, cabinets, under sinks, behind posters)
Yes
Relative Humidity
Not above 70%
Yes
Mechanical/Boiler Rooms (Assess Each)
Check OK Comments
Condition
Clean
Yes
No unusual noise or odor
Yes
No mold growth on insulation
Yes
Traps contain water
Yes
Chemical Storage
Containers capped
Yes
No evidence of an active spill
No
353 - Sink continues to run even-though off (WO #198666).
Fan Coil Units/VAV Boxes
Check OK Comments
Condition
No odors, or unusual noise or vibration
No
The Unit Ventilators on the 1st, 2nd, and 3rd Floor were operational which can lead to elevated humidity in the Summer (HVAC Contacted).