Assessor
Jeffrey Klenk
Date
Air Distribution and Terminal System (Assess 2-3 Locations per HVAC Zone)
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, noise or vibration
|
Yes
|
|
Clean, no obstructions
|
No
|
Thermostats / sensors were obstructed and/or near heat sources which could provide false room temperature allowing the room to potentially over cool or heat. Room 2B has a coffee maker near thermostat along with a nearby folder that could cover the thermostat. The thermostat in room 32 is up against a file cabinet with a printer on top (emits heat). The sensors are a blank chrome plate (typically labeled with "VAV #"). School administration is to inform staff what the sensors look like and to avoid obstructing and placing items nearby that may influence temperature reading. Staff are to move items away from the thermostats. The fan setting in portable 72 was set to "auto" instead of "on". The fan mode of the portables' thermostat is to be set to "on" at this present time. The fan mode was switched back to "on" until further notice.
|
Free from signs of moisture/mold, insects or rodents?
|
Yes
|
|
No noticeable air leaks
|
Yes
|
Check | OK | Comments |
---|---|---|
Ceiling Tiles | ||
Tight seal on all tiles
|
No
|
Room 34 (computer lab off media center) has a ceiling tile that is bowed out of the metal grid. A sprinkler head is present in the ceiling tile. Work order 190055.
|
No stained/damaged tiles indicating high RH or moisture problem
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors or unusual sounds
|
Yes
|
|
Clean, no excess dirt or moisture
|
No
|
The back side of the the exposed fins of the supply air diffusers have grime. Observed in rooms 30, 32, 39, and 43. School custodial staff are to clean the back side of the supply air diffuser fins.
|
No obstruction to air flow
|
Yes
|
|
No purposely placed obstruction indicating occupant distress
|
Yes
|
|
Location | ||
No short circuiting between supply and return
|
Yes
|
|
Doors | ||
Doors not tight or difficult to close indicating large pressure differential
|
Yes
|
Building
Check | OK | Comments |
---|---|---|
Foundation | ||
No moisture penetration or signs of mold?
|
No
|
The exterior siding of portable 162 has missing screws and a minor tear that may allow rain water to inadvertently enter the wall cavity. No moisture detected with the use of a moisture meter. Work order 190060. Salts and blistering paint observed on exterior block walls in rooms 1D and 71. Unsure if salts are old or new since school windows did undergo recent repairs. Work order 190057.
|
Doors and Windows | ||
Caulking and weather stripping in good condition
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Room is free of dust and clutter
|
Yes
|
|
No stained or damage ceiling tiles
|
No
|
Cafeteria has water stained ceiling tiles near the drywall bulkhead. Custodial staff has reported to Building Services. However a work order has been issued for Building Services to get above the drop ceiling (too high for a ladder) to observe the backside of the bulkhead to see if water impacted (mold). No water staining observed on exposed side. Work order 190044. Water stained ceiling tiles observed in gym office, girls restroom in POD 2, hallway across from electrical room 2, and room 65 (back right corner near return air grille). If not already being addressed, school custodial staff is to submit a work order to Building Services to assess source of stain and replace ceiling tile.
|
No visible mold present (walls, cabinets, under sinks, behind posters)
|
Yes
|
|
Relative Humidity | ||
Not above 70%
|
No
|
Portables 245, 246, and 247 had indoor relative humidity 71-72%. No mold observed. Outdoor relative humidity was 75% with overnight rain and morning dampness. These are newer style portables with different HVAC systems than the metal portables. In addition, fan mode operation has been modified to run continuously for the short term. No further action required.
|
Check | OK | Comments |
---|---|---|
Condition | ||
Clean
|
Yes
|
|
No unusual noise or odor
|
Yes
|
|
No mold growth on insulation
|
Yes
|
|
Traps contain water
|
Yes
|
|
Chemical Storage | ||
Containers capped
|
Yes
|
|
No evidence of an active spill
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, or unusual noise or vibration
|
No
|
The wall mounted ventilation unit in the media storage / server area (room 29) is beginning to form grime on components. Work order 190103.
|