Assessor
Jeffrey Klenk
Date
Air Distribution and Terminal System (Assess 2-3 Locations per HVAC Zone)
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, noise or vibration
|
Yes
|
|
Clean, no obstructions
|
Yes
|
|
Free from signs of moisture/mold, insects or rodents?
|
Yes
|
|
No noticeable air leaks
|
Yes
|
Check | OK | Comments |
---|---|---|
Ceiling Tiles | ||
Tight seal on all tiles
|
Yes
|
|
No stained/damaged tiles indicating high RH or moisture problem
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors or unusual sounds
|
No
|
Boy's restroom outside the gymnasium had a sewer gas odor from a dried out floor drain trap. School custodial staff is to pour 5 gallons of water into the floor drain to prime the trap.
|
Clean, no excess dirt or moisture
|
No
|
The vanes/louvers of the ceiling mounted HVAC units in room 200A had grime forming on them. School custodial staff is to clean the vanes/louvers.
|
No obstruction to air flow
|
Yes
|
|
No purposely placed obstruction indicating occupant distress
|
Yes
|
|
Location | ||
No short circuiting between supply and return
|
Yes
|
|
Doors | ||
Doors not tight or difficult to close indicating large pressure differential
|
Yes
|
Building
Check | OK | Comments |
---|---|---|
Foundation | ||
No moisture penetration or signs of mold?
|
No
|
Portable 141 had a moderate sized hole in the floor substrate at the ramp door. Work order 184168.
|
Doors and Windows | ||
Caulking and weather stripping in good condition
|
No
|
Portable 91: The opening around the exterior electrical conduit into the siding was not sealed and a dime sized puncture within the siding (right of HVAC unit). Portable 93: The opening around the exterior electrical conduit into the siding was not sealed. Portable 141: The opening around the exterior electrical conduit into the siding was not sealed. Portable 142: The opening around the exterior electrical conduit into the siding was not sealed and holes in siding from missing screws (at left of door having steps and corner ends). Work order 18471 addresses all portable findings.
|
Check | OK | Comments |
---|---|---|
Condition | ||
Room is free of dust and clutter
|
Yes
|
|
No stained or damage ceiling tiles
|
No
|
Boy's restroom outside of gym had a toilet leak at supply pipe connection at back of toilet. Work order 184163.
Water stained ceiling tiles observed in room 200A (around HVAC ceiling unit). School custodial staff is to submit a work order to Building Services if not already being addressed.
The collar around the middle sprinkler head in boys locker room (between door to gym and exit) was missing. Work order 184165.
|
No visible mold present (walls, cabinets, under sinks, behind posters)
|
Yes
|
|
Relative Humidity | ||
Not above 70%
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Clean
|
Yes
|
|
No unusual noise or odor
|
Yes
|
|
No mold growth on insulation
|
Yes
|
|
Traps contain water
|
Yes
|
|
Chemical Storage | ||
Containers capped
|
Yes
|
|
No evidence of an active spill
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, or unusual noise or vibration
|
No
|
Portable 93: From the exterior, the HVAC unit fan (located outside and bottom of the unit) was running and did not sound right. It appeared from the side, the fan component was wobbling. Work order 184166.
|