Indoor Environmental Quality General Assessment of Gorman Crossing Elementary School: July 19th, 2021 (GXGCES2021000057)

Assessor
Christopher Madden
Date

Air Distribution and Terminal System (Assess 2-3 Locations per HVAC Zone)

Ductwork (Supply and Return)
Check OK Comments
Condition
No odors, noise or vibration
No
Portable 165 - The fan setting on the thermostat was incorrectly set in the "on" position and could cause elevated humidity during the summer. The fan mode was changed to "auto" while onsite.
Clean, no obstructions
Yes
Free from signs of moisture/mold, insects or rodents?
Yes
No noticeable air leaks
Yes
Plenum
Check OK Comments
Ceiling Tiles
Tight seal on all tiles
Yes
No stained/damaged tiles indicating high RH or moisture problem
Yes
Supply Diffusers, Return Grilles, Exhaust Grilles
Check OK Comments
Condition
No odors or unusual sounds
Yes
Clean, no excess dirt or moisture
Yes
No obstruction to air flow
Yes
No purposely placed obstruction indicating occupant distress
Yes
Location
No short circuiting between supply and return
Yes
Doors
Doors not tight or difficult to close indicating large pressure differential
Yes

Building

Envelope
Check OK Comments
Foundation
No moisture penetration or signs of mold?
No
Room 77 - Flaking peeling paint indicative of door leak (WO #199003).
Doors and Windows
Caulking and weather stripping in good condition
Yes
Classrooms (Assess 2 to 3 per HVAC System Zone)
Check OK Comments
Condition
Room is free of dust and clutter
Yes
No stained or damage ceiling tiles
No
5E, Early Childhood 3 and Early Childhood Main Hall - Stained Ceiling Tile(s).
No visible mold present (walls, cabinets, under sinks, behind posters)
Yes
Relative Humidity
Not above 70%
Yes
Mechanical/Boiler Rooms (Assess Each)
Check OK Comments
Condition
Clean
Yes
No unusual noise or odor
Yes
No mold growth on insulation
No
Boiler Room - Insulation water stained (no mold growth, deferred maintenance).
Traps contain water
Yes
Chemical Storage
Containers capped
No
Kitchen - Yellow liquid labeled as water (doesn't appear to be water) needs to be relabeled to comply with OSHA's hazard communication standard.
No evidence of an active spill
Yes
Fan Coil Units/VAV Boxes
Check OK Comments
Condition
No odors, or unusual noise or vibration
Yes