Air Distribution and Terminal System (Assess 2-3 Locations per HVAC Zone)
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, noise or vibration
|
Yes
|
|
Clean, no obstructions
|
Yes
|
|
Free from signs of moisture/mold, insects or rodents?
|
Yes
|
|
No noticeable air leaks
|
Yes
|
Check | OK | Comments |
---|---|---|
Ceiling Tiles | ||
Tight seal on all tiles
|
Yes
|
|
No stained/damaged tiles indicating high RH or moisture problem
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors or unusual sounds
|
Yes
|
|
Clean, no excess dirt or moisture
|
Yes Work Order Closed by Building Maintenance
|
Visible dust accumulation observed on supply air diffusers in the hallway outside room 98. The wall return grille in portable 80 has visible dust accumulation. School custodial staff to clean now and then per their cleaning schedule.
|
No obstruction to air flow
|
Yes Work Order Closed by Building Maintenance
|
The air return grille (on wall) in portable 199 was partially obstructed. School administrator to inform staff to keep items away from return grille.
|
No purposely placed obstruction indicating occupant distress
|
Yes
|
|
Location | ||
No short circuiting between supply and return
|
Yes
|
|
Doors | ||
Doors not tight or difficult to close indicating large pressure differential
|
Yes
|
Building
Check | OK | Comments |
---|---|---|
Foundation | ||
No moisture penetration or signs of mold?
|
Yes
|
|
Doors and Windows | ||
Caulking and weather stripping in good condition
|
Yes Work Order Closed by Building Maintenance
|
The exterior side of one door on portables 79 and 80 has visible rust. Work order 231689.
A window in portable 80 shows signs of water damage (blistering, warped, no mold growth and dry per moisture meter). Work order 231693.
|
Check | OK | Comments |
---|---|---|
Condition | ||
Room is free of dust and clutter
|
Yes Work Order Closed by Building Maintenance
|
Book cases in room 28 had visible dust accumulation. School custodial is to clean.
|
No stained or damage ceiling tiles
|
Yes Work Order Closed by Building Maintenance
|
Water stained ceilings were observed in room 28, 35, and commons for rooms 31-35. If not already being addressed, school custodial staff is to submit a work order to Building Maintenance to evaluate and address.
Portable 80 has water stained ceiling tiles (several tiles, including closet). Building Maintenance was notified to inspect the condition of batt insulation and roof deck per work order 231691.
|
No visible mold present (walls, cabinets, under sinks, behind posters)
|
Yes
|
|
Relative Humidity | ||
Not above 70%
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Clean
|
Yes
|
|
No unusual noise or odor
|
Yes
|
|
No mold growth on insulation
|
Yes
|
|
Traps contain water
|
Yes
|
|
Chemical Storage | ||
Containers capped
|
Yes
|
|
No evidence of an active spill
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, or unusual noise or vibration
|
Yes Work Order Closed by Building Maintenance
|
The wall air conditioning unit in the media storage is in need of cleaning. Work order 231694.
|
Work Order Number(s)
231689,231691,231693, 231694
Issues found durring this assessment have been assigned to the above
work order(s).