School
Assessor
Jeffrey Klenk
Date
Air Distribution and Terminal System (Assess 2-3 Locations per HVAC Zone)
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, noise or vibration
|
Yes
|
|
Clean, no obstructions
|
Yes
|
|
Free from signs of moisture/mold, insects or rodents?
|
Yes
|
|
No noticeable air leaks
|
Yes
|
Check | OK | Comments |
---|---|---|
Ceiling Tiles | ||
Tight seal on all tiles
|
Yes
|
|
No stained/damaged tiles indicating high RH or moisture problem
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors or unusual sounds
|
Yes
|
|
Clean, no excess dirt or moisture
|
No
|
The exposed side of the air supply diffusers located on the stage had dust accumulation. School custodial staff is to clean dust off the diffusers.
|
No obstruction to air flow
|
Yes
|
|
No purposely placed obstruction indicating occupant distress
|
Yes
|
|
Location | ||
No short circuiting between supply and return
|
Yes
|
|
Doors | ||
Doors not tight or difficult to close indicating large pressure differential
|
Yes
|
Building
Check | OK | Comments |
---|---|---|
Foundation | ||
No moisture penetration or signs of mold?
|
Yes
|
|
Doors and Windows | ||
Caulking and weather stripping in good condition
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Room is free of dust and clutter
|
Yes
|
|
No stained or damage ceiling tiles
|
No
|
Water stained ceiling tiles observed in rooms 20 (near a supply diffuser near windows), 70 (left corner of right window), hall above water fountain across from room 11, and second floor hall above locker #716 near smoke doors across from room 14 (area pinned) along with room 13 which is the backside of the locker (drywall was dry as determined by moisture probe). If not already being addressed, school custodial staff is to submit a work order to Building Services. Minor mold growth formed on ceiling tile above locker 716. Until the source is corrected the ceiling tile should be replaced as often as necessary once mold growth becomes visible.
|
No visible mold present (walls, cabinets, under sinks, behind posters)
|
No
|
Mold growth observed on the bottom of a piano bench (on top of metal cart) located on the stage. The surface was cleaned and disinfected at the time of the finding.
|
Relative Humidity | ||
Not above 70%
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Clean
|
Yes
|
|
No unusual noise or odor
|
Yes
|
|
No mold growth on insulation
|
Yes
|
|
Traps contain water
|
Yes
|
|
Chemical Storage | ||
Containers capped
|
Yes
|
|
No evidence of an active spill
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, or unusual noise or vibration
|
No
|
The wall mounted air conditioning unit in the media server room (marked as 82 on a floor plan) has grime forming on components. Work order 201138.
|