School
Assessor
Jeffrey Klenk
Date
Air Distribution and Terminal System (Assess 2-3 Locations per HVAC Zone)
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, noise or vibration
|
Yes
|
|
Clean, no obstructions
|
Yes
|
|
Free from signs of moisture/mold, insects or rodents?
|
Yes
|
|
No noticeable air leaks
|
Yes
|
Check | OK | Comments |
---|---|---|
Ceiling Tiles | ||
Tight seal on all tiles
|
Yes
|
|
No stained/damaged tiles indicating high RH or moisture problem
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors or unusual sounds
|
Yes
|
|
Clean, no excess dirt or moisture
|
No
|
Stage supply air diffusers have visible dust accumulation. School custodial staff is to clean diffusers.
|
No obstruction to air flow
|
Yes
|
|
No purposely placed obstruction indicating occupant distress
|
Yes
|
|
Location | ||
No short circuiting between supply and return
|
Yes
|
|
Doors | ||
Doors not tight or difficult to close indicating large pressure differential
|
Yes
|
Building
Check | OK | Comments |
---|---|---|
Foundation | ||
No moisture penetration or signs of mold?
|
Yes
|
|
Doors and Windows | ||
Caulking and weather stripping in good condition
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Room is free of dust and clutter
|
Yes
|
|
No stained or damage ceiling tiles
|
No
|
Ceiling tile bowed out of ceiling grid in portable 209. Ceiling tile stain in portable 186 near supply air diffuser and light towards the thermostat. Two stained ceiling tiles in media storage 106 (off server room) below HVAC equipment (labeled on ceiling tile grid). Ceiling tile stain in room 16 and gym office. If not already being addressed, school custodial is to submit a work order to Building Services to evaluate, correct source, and replace ceiling tile.
|
No visible mold present (walls, cabinets, under sinks, behind posters)
|
No
|
Portable 125 closet walls (left and center) showed signs of moisture and confirmed with a moisture meter. Work Order 201386.
|
Relative Humidity | ||
Not above 70%
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Clean
|
Yes
|
|
No unusual noise or odor
|
Yes
|
|
No mold growth on insulation
|
Yes
|
|
Traps contain water
|
No
|
A floor drain in the girls locker room is basically covered by the locker room floor. Work Order 201480.
|
Chemical Storage | ||
Containers capped
|
Yes
|
|
No evidence of an active spill
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, or unusual noise or vibration
|
Yes
|